2017-04-20 06:07:14 | THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED | | SUBMITTALS. COMPLETE PLANS AND SPECIFICATIONS SHALL BE | | SUBMITTED FOR REVIEW FOR THE FOLLOWING ITEMS PRIOR TO | | THE INSTALLATION OF NOTED SYSTEMS: | | 1) BOILER AND ASSOCIATED PIPING AND VENT - SUBMIT AN | | EQUIPMENT SCHEDULE FOR THE BOILER, BOILER VENT PIPE(S), | | AND MANUFACTURER'S SPECIFICATIONS FOR EACH. PROVIDE A | | DIMENSIONAL ELEVATION VIEW THAT SHOWS THE TOTAL VENT | | RUN FROM THE OUTLET OF THE BOILER TO THE TERMINATION | | CAP ABOVE THE ROOF. SHOW HOW THE VENT WILL BE SUPPORTED | | AND ANCHORED TO THE ROOF STRUCTURE. | | 2) STEAM PIPING - PROVIDE STEAM PIPING DRAWINGS THAT | | SHOW THE PIPING RUNS, TYPES AND SIZES OF PIPES & PIPE | | INSULATION. | | 3) EQUIPMENT SCHEDULE AND PIPING PLAN FOR THE TANKS AND | | KETTLES USED IN THE BREWING PROCESS. | | 4)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, | | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING | | DETAILS OF THE GAS VENT(S) PER 2014 FBC-FUEL GAS SECS. | | 502 THRU 505. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|