Date |
Text |
2017-03-25 08:09:27 | 1) 2014 FBC-PLUMBING SEC.403.1.3 - SEE REQUIREMENTS FOR |
| POTTY PARITY. |
| 403.1.3 POTTY PARITY. |
| IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| SECTION 553.86, FLORIDA STATUTES. |
| EXCEPTION: THIS SECTION DOES NOT APPLY TO |
| ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA |
| STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING |
| OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 |
| PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME |
| NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL |
| OF WATER CLOSETS AND URINALS FOR MEN. |
| 2) THE TOILET COMPARTMENT IN THE MEN'S RESTROOM THAT IS |
| SHOWN AS A NON-HANDICAPPED ACCESSIBLE COMPARTMENT SHALL |
| COMPLY WITH THE 2014 FBC-ACCESSIBILITY SEC.604.8.2 PER |
| FAC SEC. SEC.213.3.1. - AMBULATORY ACCESSIBLE |
| COMPARTMENTS - (213.3.1- TOILET COMPARTMENTS.) |
| WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE |
| TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN |
| ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH |
| 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH |
| 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE |
| PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER |
| CLOSETS TOTALS SIX OR MORE FIXTURES. ) |
| 3) SHT.A-8.0 THE SIDE WALL GRAB BAR FOR THE WATER |
| CLOSET IN THE HANDICAPPED ACCESSIBLE TOILET |
| COMPARTMENTS SHALL BE LOCATED AS SPECIFIED IN 2014 |
| FBC-ACCESS. SEC.604.5.1 AND THE REAR WALL GRAB BAR |
| SHALL BE LOCATED AS SPECIFIED IN SEC.604.5.2. |
| 4) SHT. A-1.3 - EQUIPMENT PLAN NOTE #6 REFERS TO AN 80 |
| GAL. AIR COMPRESSOR BUT IT IS NOT INDICATED ON THE |
| FLOOR PLAN. SHOW THE LOCATION ON THE FLOOR PLAN AND |
| SUBMIT A COMPRESSED AIR RISER DIAGRAM FOR ANY |
| COMPRESSED AIR PIPING TO BE INSTALLED.SHOW TYPE OF |
| MATERIAL AND PIPE SIZES, VALVES, ETC. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 5) SHT. A-9.2 - DETAIL #11 - THE NOTED DIMENSIONS ON |
| THE LAVATORY DETAIL ARE VERY SMALL AND ALMOST |
| ILLEGIBLE. DETAILS SHALL BE OF SUFFICIENT CLARITY TO |
| INDICATE THE NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE. WPB AMEND. TO FBC SEC. 107.2.1. |
| 6) SHT.P5.1 - SIZE ALL SECTIONS OF THE VENT SYSTEM ON |
| THE SANITARY RISER. COMPLY WITH 2014 FBC-PLUMBING SECS. |
| 906.1 & 906.2. |
| 7) THE BRANCH VENT CONNECTING THE STACK VENTS ON THE |
| SANITARY RISER SHALL BE INCREASED BY ONE NOMINAL PIPE |
| SIZE PER 2014 FBC-PLUMBING SEC. 906.2 - VENTS EXCEEDING |
| 40 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE |
| NOMINAL PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF |
| THE VENT PIPE. |
| 8) SHT. P5.1 - A VENT IS REQUIRED BETWEEN THE TWO WATER |
| CLOSETS IN THE WOMEN'S RESTROOM PER 2014 FBC-PLUMBING |
| SEC.909.1. |
| 9) THE TRENCH DRAIN LOCATED IN ROOM #111 SHALL COMPLY |
| WITH FBC-PLUMBING TABLE 909.1 FOR THE MAXIMUM DISTANCE |
| OF THE FIXTURE TRAP FROM A VENT. THIS WILL BE CHECKED |
| IN THE FIELD AND IS NOTED HERE AS A POSSIBLE CODE |
| VIOLATION. |
| 10) SHT. P5.1 - A URINAL IS DISCHARGING INTO THE WET |
| VENT AT THE FURTHEST UPSTREAM WATER CLOSETS IN TOILET |
| ROOMS #101 & 102. THE URINAL MUST DISCHARGE DOWNSTREAM |
| OF THE HORIZONTAL WET VENT PER FBC-PLUMBING SEC.912.1. |
| 11) THE SANITARY RISER SHOWS A 2 1/2 INCH VENT. WHERE |
| DOES THIS VENT CONNECT? CLARIFY. |
| 12) SIZE THE URINAL WASTE STACKS AND VENTS. |
| FBC-PLUMBING SEC.906.1. |
| 13) THE WATER SUPPLY LINE FOR THE ICE CHEST & BEER |
| FILLER SHOWN ON THE WATER RISER SHALL BE EQUIPPED WITH |
| A BACKFLOW PREVENTER COMPLYING WITH ASSE 1022 PER |
| FBC-PLUMBING SEC.608.3. |
| 14) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE |
| EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE |
| VENT COMPLYING WITH ASSE 1012 OR CSA B64.3. |
| FBC-PLUMBING SEC.608.16.2. |
| 15) ROOM #110 SHOWS THE BOILER BLOW-OFF DISCHARGING TO |
| A FLOOR DRAIN. WASTE WATER THAT IS DISCHARGED INTO THE |
| BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT |
| GREATER THAN 140 DEGREES FARENHEIT. WHERE HIGHER |
| TEMPERATURES EXIST, APPROVED COOLING METHODS SHALL BE |
| PROVIDED. 2014 FBC SEC.701.9. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |