2017-03-25 08:09:271) 2014 FBC-PLUMBING SEC.403.1.3 - SEE REQUIREMENTS FOR
 POTTY PARITY.
 403.1.3 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
 2) THE TOILET COMPARTMENT IN THE MEN'S RESTROOM THAT IS
 SHOWN AS A NON-HANDICAPPED ACCESSIBLE COMPARTMENT SHALL
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY SEC.604.8.2 PER
 FAC SEC. SEC.213.3.1. - AMBULATORY ACCESSIBLE
 COMPARTMENTS - (213.3.1- TOILET COMPARTMENTS.)
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES. )
 3) SHT.A-8.0 THE SIDE WALL GRAB BAR FOR THE WATER
 CLOSET IN THE HANDICAPPED ACCESSIBLE TOILET
 COMPARTMENTS SHALL BE LOCATED AS SPECIFIED IN 2014
 FBC-ACCESS. SEC.604.5.1 AND THE REAR WALL GRAB BAR
 SHALL BE LOCATED AS SPECIFIED IN SEC.604.5.2.
 4) SHT. A-1.3 - EQUIPMENT PLAN NOTE #6 REFERS TO AN 80
 GAL. AIR COMPRESSOR BUT IT IS NOT INDICATED ON THE
 FLOOR PLAN. SHOW THE LOCATION ON THE FLOOR PLAN AND
 SUBMIT A COMPRESSED AIR RISER DIAGRAM FOR ANY
 COMPRESSED AIR PIPING TO BE INSTALLED.SHOW TYPE OF
 MATERIAL AND PIPE SIZES, VALVES, ETC. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) SHT. A-9.2 - DETAIL #11 - THE NOTED DIMENSIONS ON
 THE LAVATORY DETAIL ARE VERY SMALL AND ALMOST
 ILLEGIBLE. DETAILS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT.P5.1 - SIZE ALL SECTIONS OF THE VENT SYSTEM ON
 THE SANITARY RISER. COMPLY WITH 2014 FBC-PLUMBING SECS.
 906.1 & 906.2.
 7) THE BRANCH VENT CONNECTING THE STACK VENTS ON THE
 SANITARY RISER SHALL BE INCREASED BY ONE NOMINAL PIPE
 SIZE PER 2014 FBC-PLUMBING SEC. 906.2 - VENTS EXCEEDING
 40 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE
 NOMINAL PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF
 THE VENT PIPE.
 8) SHT. P5.1 - A VENT IS REQUIRED BETWEEN THE TWO WATER
 CLOSETS IN THE WOMEN'S RESTROOM PER 2014 FBC-PLUMBING
 SEC.909.1.
 9) THE TRENCH DRAIN LOCATED IN ROOM #111 SHALL COMPLY
 WITH FBC-PLUMBING TABLE 909.1 FOR THE MAXIMUM DISTANCE
 OF THE FIXTURE TRAP FROM A VENT. THIS WILL BE CHECKED
 IN THE FIELD AND IS NOTED HERE AS A POSSIBLE CODE
 VIOLATION.
 10) SHT. P5.1 - A URINAL IS DISCHARGING INTO THE WET
 VENT AT THE FURTHEST UPSTREAM WATER CLOSETS IN TOILET
 ROOMS #101 & 102. THE URINAL MUST DISCHARGE DOWNSTREAM
 OF THE HORIZONTAL WET VENT PER FBC-PLUMBING SEC.912.1.
 11) THE SANITARY RISER SHOWS A 2 1/2 INCH VENT. WHERE
 DOES THIS VENT CONNECT? CLARIFY.
 12) SIZE THE URINAL WASTE STACKS AND VENTS.
 FBC-PLUMBING SEC.906.1.
 13) THE WATER SUPPLY LINE FOR THE ICE CHEST & BEER
 FILLER SHOWN ON THE WATER RISER SHALL BE EQUIPPED WITH
 A BACKFLOW PREVENTER COMPLYING WITH ASSE 1022 PER
 FBC-PLUMBING SEC.608.3.
 14) THE POTABLE WATER CONNECTION TO THE BOILER SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER WITH AN INTERMEDIATE
 VENT COMPLYING WITH ASSE 1012 OR CSA B64.3.
 FBC-PLUMBING SEC.608.16.2.
 15) ROOM #110 SHOWS THE BOILER BLOW-OFF DISCHARGING TO
 A FLOOR DRAIN. WASTE WATER THAT IS DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT
 GREATER THAN 140 DEGREES FARENHEIT. WHERE HIGHER
 TEMPERATURES EXIST, APPROVED COOLING METHODS SHALL BE
 PROVIDED. 2014 FBC SEC.701.9.
  