2017-03-13 14:29:07 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17010884 | | 3/13/17 | | | | 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE | | NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC | | TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS | | SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ. | | INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE | | CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG | | SIZE BOILER. | | | | 2) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR | | SYSTEMS OF THE NEW RTU'S- SECTION 606.2.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|