Plan Review Notes
Plan Review Notes For Permit 17010884
Permit Number 17010884
Review Stop M
Sequence Number 2
Notes
Date Text
2017-03-13 14:29:072ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010884
 3/13/17
  
 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE
 NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC
 TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS
 SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ.
 INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE
 CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG
 SIZE BOILER.
  
 2) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR
 SYSTEMS OF THE NEW RTU'S- SECTION 606.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER