2017-03-27 09:42:46 | GAS REVIEW |
| |
| 1) THE 17" COMBUSTION AIR DUCTS ARE UNDERSIZED FOR THE |
| NEW AJAX BOILER WHICH IS SPECIFIED IN THE SUBMITTAL DOC |
| TO BE 2,100,000 BTUH. EACH OF THE TWO DUCT OPENINGS |
| SUPPLYING COMBUSTION AIR SHALL BE MINIMUM 525 SQ. |
| INCHES PER SECTION 304.6.1 FBC-14 FUEL GAS. PLEASE |
| CORRECT SHEET M2.1, AND M6.1 WHICH INDICATES THE WRONG |
| SIZE BOILER. |
| 2) THERE IS A DISCREPANCY ON THE BTU LOAD OF THE BOILER |
| ON THE MANUFACTURER'S SPECIFICATIONS AND MECHANICAL |
| DRAWINGS M2.1 & M6.1 AND THE GAS RISER ON P5.1. |
| CLARIFY. |
| 3) SHT. P5.1 - THE GAS RISER SHOWS THE BOILER AS |
| 850,000 BTUS AND THE MANUFACTURER'S SPECIFICATIONS |
| SHOWS THE BTU LOAD AS 2,100,000 BTU'S. IF THE BOILER IS |
| 2,100,000 BTU'S THE MINIMUM PIPE SIZE TO THE BOILER |
| SHALL BE 2 1/2 INCHES AND THE SIZE OF THE LINE FROM THE |
| METER SHALL BE INCREASED TO 3 INCHES. 2014 FBC-FUEL GAS |
| TABLE 402.4 (2). |
| 4) THE GAS LINE TO THE GAS WATER HEATER IS UNDERSIZED. |
| THE MINIMUM SIZE SHALL BE 1 1/4 INCHES. 2014 FBC-FUEL |
| GAS TABLE 402.4 (2). |
| 5) THE AJAX BOILER DRAWING # G62200 APPEARS TO SHOW |
| VENTS FOR THE SAFETY VALVES COMBINED WITH THE VENTS FOR |
| THE GAS REGULATOR. THE VENT FOR THE GAS REGULATOR SHALL |
| BE RUN INDEPENDENTLY TO THE OUTDOORS AND SHALL SERVE |
| ONLYY A SINGLE DEVICE VENT. 2014 FBC-FUEL GAS SEC. |
| 410.3.1. |
| 6) SHT. M2.1 - ROOM #110 - SHOWS A 12 INCH ROUND DUCT |
| UP THROUGH THE ROOF BUT IT IS NOT IDENTIFIED AS TO ITS |
| PURPOSE. CLARIFY. |
| |
| THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED |
| SUBMITTALS. COMPLETE PLANS AND SPECIFICATIONS SHALL BE |
| SUBMITTED FOR REVIEW FOR THE FOLLOWING ITEMS PRIOR TO |
| THE INSTALLATION OF NOTED SYSTEMS: |
| 1) BOILER AND ASSOCIATED PIPING AND VENT - SUBMIT AN |
| EQUIPMENT SCHEDULE FOR THE BOILER, BOILER VENT PIPE(S), |
| AND MANUFACTURER'S SPECIFICATIONS FOR EACH. PROVIDE A |
| DIMENSIONAL ELEVATION VIEW THAT SHOWS THE TOTAL VENT |
| RUN FROM THE OUTLET OF THE BOILER TO THE TERMINATION |
| CAP ABOVE THE ROOF. SHOW HOW THE VENT WILL BE SUPPORTED |
| AND ANCHORED TO THE ROOF STRUCTURE. |
| 2) STEAM PIPING - PROVIDE STEAM PIPING DRAWINGS THAT |
| SHOW THE PIPING RUNS, TYPES AND SIZES OF PIPES & PIPE |
| INSULATION. |
| 3) EQUIPMENT SCHEDULE AND PIPING PLAN FOR THE TANKS AND |
| KETTLES USED IN THE BREWING PROCESS. |
| |