2017-03-07 15:37:46 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| 1) EOR 61G DOCUMENTS ARE REQUIRED TO BE WITH THIS |
| PERMIT AND WILL ALLOOWED TO BE SUBMITTED AS A REVISION |
| TO THIS PERMIT, BUT PRIOR TO THE SHOP DRAWINGS |
| SUBMITTAL. |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| PLEASE DO NOT MISUNDERSTAND AND ENSURE COMPLIANCE WITH |
| THE ABOVE. |
| |
| |
| |
| 2) A MONITORED FIRE ALARM SYSTEM IS REQUIRED TO MONITOR |
| THE FIRE SPRINKLER SYSTEM PER NFPA 101, 5TH EDITION. |
| |
| 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A |
| MULTIPLE OCCUPANCY PROTECTED AS A MIXED OCCUPANCY (SEE |
| 6.1.14) SHALL BE PERMITTED TO BE SERVED BY A COMMON |
| FIRE ALARM SYSTEM, PROVIDED THAT THE INDIVIDUAL |
| REQUIREMENTS OF EACH OCCUPANCY ARE MET. |
| |
| |
| PLEASE PROVIDE A FIRE ALARM FOR MONIORTING THE FIRE |
| SPRINKLER SYSTEM. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |