Plan Review Notes
Plan Review Notes For Permit 17010884
Permit Number 17010884
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-03-07 15:37:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) EOR 61G DOCUMENTS ARE REQUIRED TO BE WITH THIS
 PERMIT AND WILL ALLOOWED TO BE SUBMITTED AS A REVISION
 TO THIS PERMIT, BUT PRIOR TO THE SHOP DRAWINGS
 SUBMITTAL.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PLEASE DO NOT MISUNDERSTAND AND ENSURE COMPLIANCE WITH
 THE ABOVE.
  
  
  
 2) A MONITORED FIRE ALARM SYSTEM IS REQUIRED TO MONITOR
 THE FIRE SPRINKLER SYSTEM PER NFPA 101, 5TH EDITION.
  
 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A
 MULTIPLE OCCUPANCY PROTECTED AS A MIXED OCCUPANCY (SEE
 6.1.14) SHALL BE PERMITTED TO BE SERVED BY A COMMON
 FIRE ALARM SYSTEM, PROVIDED THAT THE INDIVIDUAL
 REQUIREMENTS OF EACH OCCUPANCY ARE MET.
  
  
 PLEASE PROVIDE A FIRE ALARM FOR MONIORTING THE FIRE
 SPRINKLER SYSTEM.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  