2017-03-17 15:24:46 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| FROM PREVIOUS LIST: |
| |
| 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS |
| FOR THE MILL, FBC 107. |
| |
| 2ND REVIEW, A DRAWING WAS PROVIDED. PROVIDE SPEC SHEETS |
| AND INSTALLATION INSTRUCTIONS SO THAT ANY MANUFACTURER |
| REQUIREMENTS CAN BE VERIFIED. THIS MAY BE SENT VIA |
| EMAIL FOR REVIEW. SEE NEW COMMENT REGARDING TWO SETS |
| REQUIRED. WHEN ADDRESSING THAT COMMENT, PROVIDE TWO |
| PAPER SETS FOR ISSUANCE. |
| |
| 9. SEE IMPACT FEE REVIEW. |
| |
| NEW COMMENTS: |
| |
| 10. FBC 107, TWO COMPLETE COLLATED SETS ARE REQUIRED |
| FOR PERMIT ISSUANCE. TWO PLAN SETS WERE PROVIDED BUT |
| ONLY ONE SET OF SUPPORTING DOCUMENTS WAS PROVIDED. THE |
| SET WAS STAPLED ON THE SIDE OF ONE PLAN. IT IS NOT |
| NECESSARY TO STAPLE IT IN THIS MANNER (WE PREFER TWO |
| IDENTICAL CLIPPED SETS OF SUPPORTING DOCUMENTS, TABBED |
| ONLY IF DOCUMENTS ARE EXTREMELY EXTENSIVE). DUE TO WORK |
| LOAD, THERE ARE NOT ANY STAFF PEOPLE AVAILABLE TO |
| PERFORM COPY DUTIES. PROVIDE A SECOND IDENTICAL SET. |
| |
| 11. IS A8.0 A NEW SHEET? I WAS UNABLE TO LOCATE THE OLD |
| SHEET. SEE FBC A 604.4, SEAT HEIGHT TO BE MEASURED AT |
| TOP OF SEAT, DETAIL SHOWS MEASUREMENT TO TOP OF LID. IF |
| THIS SHEET IS REVISED FOR ANOTHER TRADE, REVISE ALL |
| AFFECTED DETAILS. IF IT IS NOT REVISED FOR ANOTHER |
| TRADE, PLEASE ADVISE AND THIS WILL BE REDLINED. PLEASE |
| HAVE THIS CORRECTED ON ALL FUTURE SUBMITTALS. |
| |
| 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISO: |
| |
| FIRE SPRINKLERS REQUIRED FOR C.O. |
| |
| MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B |
| 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE |
| PUBLIC WAY. |
| |
| A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE |
| REQUIRED. PER ARCHITECT, ALL OUTDOOR EQUIPMENT IS |
| LOCATED ON THE ROOFTOP. ELEVATION CERTIFICATE IS TO |
| INCLUDE ROOFTOP EQUIPMENT. IF ANY EQUIPMENT IS AT |
| GRADE, A REVISION SHOWING ELEVATION IS REQUIRED |
| (INCLUDING OTHER TENANTS). |
| |
| ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT |
| ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES, |
| TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. |
| |