Plan Review Notes
Plan Review Notes For Permit 17010884
Permit Number 17010884
Review Stop B
Sequence Number 2
Notes
Date Text
2017-03-17 15:24:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS
 FOR THE MILL, FBC 107.
  
 2ND REVIEW, A DRAWING WAS PROVIDED. PROVIDE SPEC SHEETS
 AND INSTALLATION INSTRUCTIONS SO THAT ANY MANUFACTURER
 REQUIREMENTS CAN BE VERIFIED. THIS MAY BE SENT VIA
 EMAIL FOR REVIEW. SEE NEW COMMENT REGARDING TWO SETS
 REQUIRED. WHEN ADDRESSING THAT COMMENT, PROVIDE TWO
 PAPER SETS FOR ISSUANCE.
  
 9. SEE IMPACT FEE REVIEW.
  
 NEW COMMENTS:
  
 10. FBC 107, TWO COMPLETE COLLATED SETS ARE REQUIRED
 FOR PERMIT ISSUANCE. TWO PLAN SETS WERE PROVIDED BUT
 ONLY ONE SET OF SUPPORTING DOCUMENTS WAS PROVIDED. THE
 SET WAS STAPLED ON THE SIDE OF ONE PLAN. IT IS NOT
 NECESSARY TO STAPLE IT IN THIS MANNER (WE PREFER TWO
 IDENTICAL CLIPPED SETS OF SUPPORTING DOCUMENTS, TABBED
 ONLY IF DOCUMENTS ARE EXTREMELY EXTENSIVE). DUE TO WORK
 LOAD, THERE ARE NOT ANY STAFF PEOPLE AVAILABLE TO
 PERFORM COPY DUTIES. PROVIDE A SECOND IDENTICAL SET.
  
 11. IS A8.0 A NEW SHEET? I WAS UNABLE TO LOCATE THE OLD
 SHEET. SEE FBC A 604.4, SEAT HEIGHT TO BE MEASURED AT
 TOP OF SEAT, DETAIL SHOWS MEASUREMENT TO TOP OF LID. IF
 THIS SHEET IS REVISED FOR ANOTHER TRADE, REVISE ALL
 AFFECTED DETAILS. IF IT IS NOT REVISED FOR ANOTHER
 TRADE, PLEASE ADVISE AND THIS WILL BE REDLINED. PLEASE
 HAVE THIS CORRECTED ON ALL FUTURE SUBMITTALS.
  
 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISO:
  
 FIRE SPRINKLERS REQUIRED FOR C.O.
  
 MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B
 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE
 PUBLIC WAY.
  
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED. PER ARCHITECT, ALL OUTDOOR EQUIPMENT IS
 LOCATED ON THE ROOFTOP. ELEVATION CERTIFICATE IS TO
 INCLUDE ROOFTOP EQUIPMENT. IF ANY EQUIPMENT IS AT
 GRADE, A REVISION SHOWING ELEVATION IS REQUIRED
 (INCLUDING OTHER TENANTS).
  
 ANY PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES,
 TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION.
  