Plan Review Notes For Permit 17010884 |
Permit Number |
17010884 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-21 15:03:00 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. PLEASE SHOW DIMENSION ON THE PLAN OF THE MIRROR IN | | THE ACCESSIBLE BATHROOM STALL. PER FBC ACC 603.3 | | MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES | | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE | | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM | | ABOVE THE FINISH FLOOR OR GROUND. | | | | 2.PLEASE INDICATE ON PLAN WHICH URINAL IS ACCESSIBLE. | | PER FBC ACC 213.3.3 | | | | 3. SHT. P-5.1 THE FLOOR DRAINS AND TRENCH DRAINS ARE | | NOT VENTED. PER FBC PL 901.2.1 | | | | 4. PLEASE COMPLY WITH MECHANICAL COMMENTS. PER WPB | | AMEND TO FBC 107.2.1 | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|