Plan Review Notes For Permit 17010884 |
Permit Number |
17010884 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-21 15:43:17 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | SEC. 402.4.1. | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | | | 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | SEC. 502 THRU 505. | | | | 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402. | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|