2017-02-07 13:57:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET ALS1.0 - THERE A SEVERAL OCCUPANCY TYPES |
| INDICATED; HOWEVER, IS THIS A MIXED OCCUPANCY OR |
| SEPARATED OCCUPANCY AND WHAT OCCUPANCY TYPE IS THE |
| PROPOSED PROJECT DESIGNED UNDER. |
| |
| PER THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION |
| CODE, NFPA 101 |
| |
| 6.1 CLASSIFICATION OF OCCUPANCY. |
| 6.1.1 GENERAL. |
| 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR |
| STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 |
| THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE |
| SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| JURISDICTION WHERE THERE IS A QUESTION OF PROPER |
| CLASSIFICATION IN ANY INDIVIDUAL CASE. |
| |
| 6.1.14 MULTIPLE OCCUPANCIES. |
| 6.1.14.1 GENERAL. |
| 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| |
| 6.1.14.2 DEFINITIONS. |
| 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. |
| 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| THE OCCUPANCIES ARE INTERMINGLED. |
| 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE |
| RESISTANCE?RATED ASSEMBLIES. |
| 6.1.14.3 MIXED OCCUPANCIES. |
| 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| |
| PLEASE PROVIDE THE SPECIFICS FOR COMPLIANCE WITH THE |
| ABOVE NOTED AND RELATED CODES. |
| |
| |
| |
| 2) SHEET ALS 1.0 - A BOLIER IS INDICATED IN ROOM 110. |
| |
| PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS FOR THE |
| BOLIER INCLUDING EXPLOSION HAZARD INFORMATION. PROVIDE |
| ANY RELATED CONSTRUCTION RELATED REVISONS FOR EXPLOSION |
| PROTECTION IF APPLICABLE. |
| |
| |
| 3) SHEET ALS 1.0 - A MILL IS INDICATED IN ROOM 112. |
| |
| PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS FOR THE |
| MILL INCLUDING EXPLOSION HAZARD INFORMATION. PROVIDE |
| ANY RELATED CONSTRUCTION RELATED REVISONS FOR EXPLOSION |
| PROTECTION IF APPLICABLE. |
| |
| PLEASE PROVIDE A NOTE AND/OR REVSIONS RELATED TO MILL |
| ROOM REGARDING ALL WIRING, LIGHTS, SWITCHES, |
| HOUSEKEEPING, ETC, ARE ALL EXPLOSION PROOF, IF |
| APPLICABLE. |
| |
| |
| |
| 4) SHEET A 1.0 - THE INDICATED OCCUPANCY LOAD; 221, AND |
| EXIT CAPACITY; 117, CALCULATIONS DO NOT MATCH. |
| ADDITIONALLY, THERE IS AN INDICATION OF THE EXIT |
| CAPACITY CALCULATION OF .2 LEVEL TRAVEL; HOWEVER, THE |
| TWO EXITS ARE INDICATED WITH STAIRS. |
| |
| PER NFPA 101, CHAPTER 7 MEANS OF EGRESS, STAIRS SHALL |
| BE CALCULATED WITH .3. THE EXIT CAPACITY APPEARS TO BE |
| SUFFICIENT; HOWEVER, THE CALULATIONS NEED CORRECTION. |
| |
| PLEASE PROVIDE CORRECTIONS. |
| |
| |
| |
| 5) SHEET ALS 1.0 - A DOUBLE DOOR EXIT IS INDICATING |
| LEADING INTO THE PATIO. THERE ARE TABLES AND CHAIRS |
| INDICATED IN THE PATIO. THE DOOR SWINGS INTO THE PATIO |
| AND INTO AND RESTRICTING THE EXIT PATHWAY. |
| |
| PER NFPA 101, CHAPTER 7 MEANS OF EGRESS |
| |
| PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| OPEN. |
| |
| PLEASE PROVIDE FOR THE REQUIRED WIDTH. |
| |
| |
| 6) SHEET E2.1 & A1.1 - THERE IS ONLY ONE EXIT LIGHTS |
| INDICATED ON THE ON E2.1 AT THE FRONT DOOR. THERE ARE |
| NO OTHER EXITS LIGHTS AS INDICATED ON A1.1 IN THE PATH |
| OF TRAVEL. |
| |
| PLEASE ADD ALL APPLICABLE EXIT LIGHTS PER ALL EXIT PATH |
| AND EXIT DISCHARGE LOCATION. PLEASE ENSURE TO ADD NA |
| EXIT LIGHT INSIDE THE LOADING AREA AT THE STAIRS |
| LEADING TO OTHER EXIT ACCESS. |
| |
| |
| |
| 7) SHEET E2.1- THERE SOME EMERGENCY LIGHTING INDICATED; |
| HOWEVER, IT MAY NOT PROVIDE SUFFICIENT LIGHTING ALONG |
| THE EXXIT PATH OF TRAVEL. |
| |
| PLEASE ESURE THAT ALL EXITS AND EXIT PATHS HAVE THE |
| REQUIRED EMERGENCY LIGHT LUMINATION PER THE OCCUPANCY |
| CLASSIFICATION CODE REQUIREMENTS AS REQUIRED BY # 1 |
| ABOVE. |
| |
| |
| |
| 8) NO SHEET - A NOTE INDICATING THAT A FIRE SPRINKLER |
| SHOP DRAWING WILL BE PROVIDED; HOWEVER, IT APPEARS IT |
| WILL BE A NEW SYSTEM. |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| THIS INFORMATION MAY BE PROVIDED WITH AN OFFICIAL |
| SIGNED AND SEALED DRAWING OR LETTER NARRATIVE FORM A |
| QUALIFIED DESIGN PROFESSIONAL. |
| |
| PLEASE PROVIDE DOCUMENTATION PER THE REQUIRMENTS. |
| |
| |
| 9) THERE IS NO INDICATION OF ANY FIRE ALARM SYSTEM. |
| |
| PROVIDE AN APPLICABLE REFERENCE OF A FIRE ALARM SYSTEM |
| PER THE APPLICABLE OCCUPANCY CLASSIFICATION OF # 1 |
| ABOVE AND/OR FOR THE MONITORING OF THE FIRE SPRINKLER |
| SYSTEM. |
| |
| |
| |
| 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |