Plan Review Notes For Permit 17010884 |
Permit Number |
17010884 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-02 14:28:06 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | ELECTRIC SERVICE. NEC 110.9, 110.10 | | | | PROVIDE THE SERVICE WIRE AND SERVICE MAST SIZE. NEC | | 230.23 | | | | INDICATE THE MINIMUM HEIGHT REQUIRED FOR THE OVERHEAD | | SERVICE ABOVE THE ALLEWAY TO THE BOTTOM OF THE SERVICE | | DRIP LOOP. NEC 230.24, 230.26 | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE SERVICE MAIN DISCONNECTING MEANS. NEC 110.16, | | 110.22, 110.24 | | | | PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40 | | | | PROVIDE AN INTERSYSTEM BONDING BAR AT THE ELECTRICAL | | SERVICE. NEC 250.94 | | | | PROVIDE THE LOCATION OF THE LIGHTING CONTROL PANEL AND | | SWITCH BANK. NEC 110.3 | | | | PROVIDE A BOLLARD OR EQUALIVENT PROTECTION DETAIL FOR | | THE ELECTRICAL SERVICE LOCATED IN THE DELIVERY ALLEWAY. | | NEC 110.2, 110.3, 110.11 | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | SYSTEMS, SECURITY AND DATA SYSTEMS | | | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-805-6654 | | 561-373-3701 | | [email protected] | | |
|