2017-02-02 14:28:06PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE. NEC 110.9, 110.10
  
 PROVIDE THE SERVICE WIRE AND SERVICE MAST SIZE. NEC
 230.23
  
 INDICATE THE MINIMUM HEIGHT REQUIRED FOR THE OVERHEAD
 SERVICE ABOVE THE ALLEWAY TO THE BOTTOM OF THE SERVICE
 DRIP LOOP. NEC 230.24, 230.26
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE MAIN DISCONNECTING MEANS. NEC 110.16,
 110.22, 110.24
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40
  
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE ELECTRICAL
 SERVICE. NEC 250.94
  
 PROVIDE THE LOCATION OF THE LIGHTING CONTROL PANEL AND
 SWITCH BANK. NEC 110.3
  
 PROVIDE A BOLLARD OR EQUALIVENT PROTECTION DETAIL FOR
 THE ELECTRICAL SERVICE LOCATED IN THE DELIVERY ALLEWAY.
 NEC 110.2, 110.3, 110.11
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS
  
  
  