2017-02-16 10:53:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY, FBC EB |
| CHAPTER 10. REVISE PLAN TO SHOW COMPLIANCE. NO |
| INFORMATION REGARDING BUILDING AREA FBC TABLE 503 WAS |
| PROVIDED. |
| |
| REVISE PLAN TO INCLUDE INFORMATION REGARDING THE OTHER |
| TENANT SPACES, INCLUDING SF AREA AND OCCUPANCY |
| CLASSIFICATION, AND BUILDING TYPE FBC CHAPTER 6. |
| |
| REVISE PLAN TO INCLUDE PREVIOUS OCCUPANCY, FBC EB 1012, |
| TABLES 1012.4, 1012.5, 1012.6. |
| |
| REVISE PLAN TO SHOW COMPLIANCE WITH ALL CHANGE OF |
| OCCUPANCY REQUIREMENTS FBC EB 1012. |
| |
| NO SITE PLAN PROVIDED; THIS WILL LIKELY BE REQUIRED FBC |
| EB TABLE 1012.6. |
| |
| 2. THIS APPEARS TO BE A NON SPRINKLERED BUILDING. |
| SPRINKLERS ARE PROPOSED. SEE FIRE COMMENTS; THIS IS |
| ALSO APPLICABLE FOR BUILDING. IF THE BUILDING IS |
| CURRENTLY FULLY SPRINKLERED, REVISE PLAN TO STATE. IF A |
| NEW SPRINKLER SYSTEM IS PROPOSED, PROVIDE SPRINKLER |
| INFORMATION. |
| |
| IF A NEW SPRINKLER SYSTEM IS PROPOSED, AN ENGINEERING |
| PERMIT IS REQUIRED. CONTACT ENGINEERING DEPARTMENT AND |
| SUBMIT ANY REQUIRED APPLICATIONS. |
| |
| 3. PROVIDE SPEC SHEETS AND INSTALLATION INSTRUCTIONS |
| FOR THE MILL, FBC 107. |
| |
| 4. DETAIL 13-A9.0, THE FOOT REST APPEARS TO OBSTRUCT |
| THE REQUIRED TOE CLEARANCE, FBC A 306.2. REVISE PLAN TO |
| SHOW COMPLIANCE. |
| |
| 5. REVISE PLAN TO INCLUDE FINISHED FLOOR ELEVATION, FBC |
| B 1612. THIS IS CONSIDERED A SUBSTANTIAL IMPROVEMENT. |
| |
| 6. PROVIDE A SITE PLAN OR SURVEY WHICH INCLUDES ALL |
| EQUIPMENT AT GRADE. IF ALL EQUIPMENT SERVICING THE |
| BUILDING IS LOCATED ON THE ROOF, REVISE PLAN TO NOTE, |
| FBC B 1612. |
| |
| 7. SHEET A7.0 INCLUDES A NOTE REGARDING PANIC HARDWARE. |
| SEE FBC B 1008.1.10; WILL BOTH EXIT DOORS INCLUDE PANIC |
| BARS? REVISE PLAN TO CLARIFY. |
| |
| 8. PLAN SPECIFIES TRULITE STOREFRONT SYSTEM AND DOORS, |
| OVERHEAD DOORS. PROVIDE PRODUCT APPROVALS, FBC 107. ANY |
| PRODUCT APPROVALS NOT SUBMITTED PRIOR TO PERMIT |
| ISSUANCE WILL REQUIRE A REVISION, WITH ADDITIONAL FEES, |
| TO BE SUBMITTED AND APPROVED PRIOR TO INSTALLATION. |
| |
| 9. SEE IMPACT FEE REVIEW. |
| |
| THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISO: |
| |
| MEANS OF EGRESS ILLUMINATION IN COMPLIANCE WITH FBC B |
| 1006 REQUIRED, INCLUDING THE EXIT DISCHARGE TO THE |
| PUBLIC WAY. |
| |
| A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE |
| REQUIRED. THIS SHOULD INCLUDE ALL EQUIPMENT SERVICING |
| THE BUILDING. |
| |