2017-02-02 11:48:40 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010882 | | 2/2/17 | | | | 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS | | WITH CORREPONDING DETAILS ON THE PLANS. CLARIFY IF EACH | | NEW TENANT SPACE HAS IT'S OWN INDIVIDUAL AC SYSTEM. | | | | 2) THE PROJECT HAS BEEN CLASSIFIED AS A LEVEL 2 | | ALTERATION. REFER TO SECTION 809.1 & 809.2 FBC-14 | | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|