2017-02-02 11:48:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010882
 2/2/17
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORREPONDING DETAILS ON THE PLANS. CLARIFY IF EACH
 NEW TENANT SPACE HAS IT'S OWN INDIVIDUAL AC SYSTEM.
  
 2) THE PROJECT HAS BEEN CLASSIFIED AS A LEVEL 2
 ALTERATION. REFER TO SECTION 809.1 & 809.2 FBC-14
 EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  