Plan Review Notes
Plan Review Notes For Permit 17010881
Permit Number 17010881
Review Stop M
Sequence Number 2
Notes
Date Text
2017-06-21 17:11:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010881
 6/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED IT BELOW. PLEASE NOTE THAT ADDITIONAL OUTSIDE
 AIR MAY BE REQUIRED WHICH COULD IMPACT THE AC SYSTEMS.
  
 THE PROJECT HAS BEEN IDENTIFIED AS A LEVEL 2 ALTERATION
 FBC-14 EXISTING BUILDING CODE. REFER TO SECTION 809.2
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING AC
 SYSTEMS THAT LIST THE MAKES AND MODELS, THE COOLING AND
 HEATING CAPACITIES, AND SUPPLY CFMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  