2017-02-01 16:58:41 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010881 | | 2/1/2017AIR. | | | | 1) THE PROJECT HAS BEEN IDENTIFIED AS A LEVEL 2 | | ALTERATION FBC-14 EXISTING BUILDING CODE. REFER TO | | SECTION 809.2 AND PROVIDE MINIMUM VENTILATION | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) PROVIDE MECHANICAL ALTERATION PLANS BASED ON THE NEW | | FLOOR PLAN LAYOUT. | | | | 3) COMPLY WITH BUILDING PLAN REVIEW COMMENTS TO FURTHER | | CLARIFY THE SCOPE OF THE PROJECT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|