2017-01-28 09:30:20 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17010881 |
| ADD: 4047 OKEECHOBEE BLVD. SUITE # 105& 106. |
| CONT: MOSS DEVCO INC. |
| TEL:561-876-4570 |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. JAN. 28/2017 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THERE IS A DISCREPANCY IN THE LOCATION |
| OF THE PROPOSED WORK TO BE COMPLETED UNDER THIS PERMIT. |
| THE PERMIT APPLICATION INDICATES WORK IS TO OCCUR IN |
| UNITS 106 & 107, WHEREAS THE PLANS STATE WORK IS TO BE |
| COMPLETED IN UNITS 105& 106? PLEASE CORRECT BEFORE THE |
| NEXT SUBMISSION TO THE BUILDING DEPARTMENT. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION OF PROPOSED WORK. |
| |
| 2A) SHEET S-1 DISCREPANCY IN PLANS. 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. 2014 FBC-B TABLE 603 |
| RATINGS ON THE ROOF FRAMING MEMBERS. THE SHEET S-1 |
| INDICATES THE TYPE OF CONSTRUCTION AS A BUILDING TYPE |
| I-A REQUIRING 1 1/2 HOUR FIRE RATING, THE SHEET S-1 |
| INDICATES THE BUILDING IS FIRE SPRINKLERED, UNPROTECTED |
| BOTH IA AND IB HAVE FIRE PROTECTED ROOF FRAMING |
| MEMBERS. UNDER THE HEADING OF CONSTRUCTION LISTED: 1 |
| STORY CBS WITH METAL JOIST TYPE IIB NOT REQUIRING ANY |
| FIRE PROTECTION ON THE ROOF FRAMING MEMBERS OR |
| SECONDARY MEMBERS. PLEASE IDENTIFY THE TYPE OF |
| CONSTRUCTION AND CORRECT THE PLANS ACCORDINGLY. |
| |
| 2B) SHEET S2 ON THE LEFT SIDE OF THE SHEET IS A NOTE; |
| NEW ONE HOUR PARTY WALLS (BY OTHERS). ARE THESE NEW |
| WALLS FURTHER SEPARATING THE BUILDING INTO SMALLER BUT |
| MORE BUILDINGS? PARTY WALLS ARE FIRE WALLS. 706.1.1 |
| PARTY WALLS. ANY WALL LOCATED ON A LOT LINE BETWEEN |
| ADJACENT BUILDINGS, WHICH IS USED OR ADAPTED FOR JOINT |
| SERVICE BETWEEN THE TWO BUILDINGS, SHALL BE CONSTRUCTED |
| AS A FIRE WALL IN ACCORDANCE WITH SECTION 706. PARTY |
| WALLS SHALL BE CONSTRUCTED WITHOUT OPENINGS AND SHALL |
| CREATE SEPARATE BUILDINGS. |
| THESE WALLS WILL NEED TO BE PERMITTED AND COMPLETED |
| BEFORE THE TENANT PERMITS CAN BE PERMITTED AND |
| CERTIFICATE OF COMPLETION CAN OCCUR. |
| |
| 3) PLEASE NOTE THAT IN UNIT # 107 THE CONVERSION OF A |
| KITCHEN FROM A RESTROOM DOES NOT SHOW ON ANY OF THE |
| ISSUED PERMITS IN THE ELECTRONIC FILE SYSTEM FILE NET. |
| ALL WORK AS SHOWN WILL BE CONSIDERED NEW WORK. 2014 |
| FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR |
| AGENT AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489 |
| WHO INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, |
| DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR |
| STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER, |
| REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT RESISTANT |
| COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR |
| FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD |
| RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS |
| REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE |
| DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING |
| OFFICIAL AND OBTAIN THE REQUIRED PERMIT. |
| |
| 4) SHEET S3 IS THE LIFE SAFETY PLAN, PLEASE PROVIDE THE |
| LIFE SAFETY PLAN SHOULD HAVE ALL OF THE FURNITURE, |
| KIOSK SHOWN ON THE PLANS. PLEASE PROVIDE WHAT THE USAGE |
| OF THIS SPACE WILL BE USED FOR, WITH PASS THROUGH AND A |
| KITCHEN? 2014 FBC-B 302.1. A ROOM OR SPACE THAT IS |
| INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR |
| DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE |
| REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE |
| PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED. |
| WHERE A STRUCTURE IS PROPOSED FOR A PURPOSE THAT IS NOT |
| SPECIFICALLY PROVIDED FOR IN THIS CODE, SUCH STRUCTURE |
| SHALL BE CLASSIFIED IN THE GROUP THAT THE OCCUPANCY |
| MOST NEARLY RESEMBLES, ACCORDING TO THE FIRE SAFETY AND |
| RELATIVE HAZARD INVOLVED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |