Plan Review Notes For Permit 17010879 |
Permit Number |
17010879 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-02 10:22:03 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010879 | | 2/217 | | | | 1) THE PROPOSED PROJECT HAS BEEN CLASSIFIED AS A LEVEL | | 2 ALTERATION ON SHEET S-1. REFER TO SECTION 809.1 | | FBC-14 EXISTING BUILDING CODE AND PROVIDE MINIMUM | | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER | | TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT | | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR | | AIR. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|