2017-01-23 18:24:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT AND ROOF SLOPE. FBC
 107.2.1
  
 2) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTING OF THE BASE SHEET ON THE FLAT ROOF
 AREAS. THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM THAT
 WAS SELECTED (W-11) IS -52.5 PSF WHICH IS NOT ADEQUATE
 FOR ROOF ZONES 2 AND 3. SEE NOTE 7 ON PAGE 2 OF THE
 PRODUCT APPROVAL.
  
  
  