2017-01-31 08:21:101ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010802
 1/31/17
  
 1) PROVIDE O/A CALCULATIONS FOR THE STORAGE ROOM.
  
 2) CLARIFY THE PURPOSE OF EF-2 IN THE STORAGE ROOM AND
 PROVIDE AN EXHAUST VENTILATION CALCULATION. PLEASE NOTE
 AN INDEPENDENT EXHAUST SYSTEM MAY BE REQUIRED PER
 COMMENT #3 BELOW.
  
 3) CLARIFY WHAT MATERIALS OR CHEMICALS WILL BE STORED
 IN THE STORAGE ROOM. REFER TO SECTION 414.1.3 FBC-14
 BUILDING AND, IF APPLICABLE, PROVIDE A REPORT
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 AND/OR OPEN SYSTEM AND SUBDIVIED TO SEAPARATELY ADDRESS
 HAZARDOUS MATERIALS CLASSIFICATION CATEGORIES BASED ON
 TABLE 307.1(1) AND 307.1(2).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  