2017-02-01 10:54:24INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS CARD READERS, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS FOR
 MODIFICATIONS; SEE VERBIAGE IN CODE.
 4. FUTURE GENERATOR NOT PART OF SCOPE. CLARIFICATION
 REQUIRED
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE