Plan Review Notes For Permit 17010799 |
Permit Number |
17010799 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-05-26 16:40:32 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #17010799 | | 5/26/17 | | | | RESULTS: DENIED. | | | | 1) COMMENT #1 FROM THE PREVIOUS (2ND) REVIEW HAS NOT | | BEEN COMPLETELY ADDRESSED. THE PLANS INDICATE THE O/A | | INTAKES LOCATED ON THE NORTH AND EAST SIDES OF THE | | BUILDING ARE ONLY 5' FROM THE PROPERTY LINES, HOWEVER A | | MINIMUM 10' CLEARANCE IS REQUIRED- SECTION 401.4. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|