2017-05-26 16:40:323RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17010799
 5/26/17
  
 RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE PREVIOUS (2ND) REVIEW HAS NOT
 BEEN COMPLETELY ADDRESSED. THE PLANS INDICATE THE O/A
 INTAKES LOCATED ON THE NORTH AND EAST SIDES OF THE
 BUILDING ARE ONLY 5' FROM THE PROPERTY LINES, HOWEVER A
 MINIMUM 10' CLEARANCE IS REQUIRED- SECTION 401.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  