2017-05-26 08:26:21 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17010799 |
| ADD: 539 OGSTON ST. |
| CONT: CANO INC. |
| TEL: 561-543-1290 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: FRI. MAY 26/ 2017 |
| ACTION: DENIED |
| |
| 1-5) COMPLIED. |
| |
| 6) 3RD REQUEST. BUILDING # 1. BEFORE A PERMIT TO |
| CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| 7A) SEMI-COMPLIED. THE FP-1 FIRE SPRINKLER PLANS |
| APPEARS TO BE SIGNED WITH A 1 ? INCH DIGITAL SIGNATURE |
| AND SEAL. |
| |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS. |
| |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| 61G15-23.002 SEALS ACCEPTABLE TO THE BOARD. |
| (2) WET SEALS, EMBOSSING SEALS AND DIGITALLY CREATED |
| SEALS SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER |
| AND SHALL BE OF A DESIGN SIMILAR TO THOSE SET FORTH IN |
| SUBSECTIONS. |
| |
| |
| 1ST ROUND COMMENTS. FIRE SPRINKLER PLANS REQUIRED. W. |
| P. B. ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER |
| DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH |
| INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR |
| MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR |
| CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA |
| STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR |
| FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN |
| EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION |
| CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT |
| MORE THAN 49 HEADS, NOT WITHSTANDING THE SIZE OF THE |
| EXISTING FIRE SPRINKLER SYSTEM. |
| |
| 7B) NEW COMMENT: SHEET FP-1 PLEASE MAKE SUTE THE |
| CORRECT ADDRESS IS ON THE PLANS, NO HAND WRITTEN |
| ADDRESS. THE ORIGINAL 539 OGSTON ST. IS THE CORRECT |
| ADDRESS. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |