Plan Review Notes For Permit 17010799 |
Permit Number |
17010799 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-05-08 11:15:11 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17010799 | | 5/8/17 | | | | RESULTS: DENIED | | | | PLEASE ADDRESS THE COMMENTS BELOW. | | | | 1) AFTER FURTHER REVIEW IT APPEARS THAT THE LOCATIONS | | OF OUTSIDE AIR INTAKES FOR THE AHU'S MAY BE NOT IN | | COMPLIANCE WITH THE CLEARANCE DISTANCE REQUIRERMENTS | | OUTLINED IN SECTION 401.4. SEE COMMENT # FROM THE 1ST | | REVIEW AND PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS | | FROM THE O/A INTAKES TO PROPERTY LINES, STREETS, | | ALLEYS, OR PARKING AREAS. | | | | 2) IT APPEARS THAT AIR HANDLERS ARE BEING INSTALLED IN | | THE ATTIC SPACE OF THE BUILDING WHICH IS PROHIBITED PER | | SECTION C403.2.7.6 FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|