Plan Review Notes
Plan Review Notes For Permit 17010799
Permit Number 17010799
Review Stop M
Sequence Number 2
Notes
Date Text
2017-05-08 11:15:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17010799
 5/8/17
  
 RESULTS: DENIED
  
 PLEASE ADDRESS THE COMMENTS BELOW.
  
 1) AFTER FURTHER REVIEW IT APPEARS THAT THE LOCATIONS
 OF OUTSIDE AIR INTAKES FOR THE AHU'S MAY BE NOT IN
 COMPLIANCE WITH THE CLEARANCE DISTANCE REQUIRERMENTS
 OUTLINED IN SECTION 401.4. SEE COMMENT # FROM THE 1ST
 REVIEW AND PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS
 FROM THE O/A INTAKES TO PROPERTY LINES, STREETS,
 ALLEYS, OR PARKING AREAS.
  
 2) IT APPEARS THAT AIR HANDLERS ARE BEING INSTALLED IN
 THE ATTIC SPACE OF THE BUILDING WHICH IS PROHIBITED PER
 SECTION C403.2.7.6 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER