Plan Review Notes
Plan Review Notes For Permit 17010799
Permit Number 17010799
Review Stop B
Sequence Number 2
Notes
Date Text
2017-05-05 15:41:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010799
 ADD: 539 OGSTON ST.
 CONT: CANO INC.
 TEL:
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MAY 05/ 2017
 ACTION: DENIED
  
 1A) SEMI- COMPLIED. THE COVERSHEET STILL INDICATES
 BUILDINGS 1 & 3. THE 4300 MILLER PROPERTY WAS
 SUPPOSEDLY DELETED FROM THIS PORTION OF THE PROJECT ON
 THE VARIOUS ARCHITECTURAL SHEETS BUILDING 3 IS X-ED
 THROUGH. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 1B) COMPLIED. THE 4300 MILLER PROPERTY DELETED FROM
 THIS PORTION OF THE PROJECT. NOTE TO HAVE 2 DIFFERENT
 OWNERS INVOLVED IN THE PROJECT THE DOCUMENT UNITY OF
 CONTROL WILL HAVE TO BE DEVELOPED BY THE CITY LAWYERS.
  
 1C) COMPLIED. 308.4 INSTITUTIONAL GROUP I-2. BUILDINGS
 AND STRUCTURES USED FOR MEDICAL CARE ON A 24-HOUR BASIS
 FOR MORE THAN FIVE PERSONS WHO ARE INCAPABLE OF
 SELF-PRESERVATION. THIS GROUP SHALL INCLUDE, BUT NOT BE
 LIMITED TO, THE FOLLOWING: DETOXIFICATION FACILITIES.
 ZONING REQUIREMENT: APPLIED FOR A CLASS B USE.
  
 1D)COMPLIED. THE OCCUPANCY I-2 BUILDING TYPE VA.
  
 2) SHEET A-101:
 2A) COMPLIED. BUILDING 1- BUILDING CATEGORY II/ 170
 MPH/ 3 SECOND GUST/ VULT WIND DESIGN.
  
 2B) 2ND REQUEST. SHEET A-101 SHOWS THAT BOTH TYPES OF
 FIRE SPRINKLERS NFPA 13 (903.3.1.1) AND NFPA 13R
 (903.3.1.2). WITH THE BUILDING 3 ELIMINATED FROM THIS
 PORTION OF THE PROJECT, IT IS ASSUMED THE NFPA 13R
 (903.3.1.2) WILL BE INSTALLED IN THE GROUP I-2
 OCCUPANCY. THIS IS ALLOWED BY 903.2.6 BUT IN DOING SO
 YOU CANNOT TAKE THE 25% FOR FIRE SPRINKLERS SEE TABLE
 FBC-B 705.8 FOOTNOTE FOR S (SPRINKLERS) SPRINKLERS HAVE
 TO COMPLY WITH 903.3.1.1 OR NFPA 13. PLEASE REFIGURE
 BOTH THE HEIGHT OF WALLS FROM 18 FEET IN HEIGHT AND
 WINDOW AND DOOR OPENINGS AT 10 % IF 13R SPRINKLERS ARE
 TO BE INSTALLED. CLARIFY ALSO ON SHEET A-101.
 1ST ROUND OF COMMENTS. BUILDING # 1 SHOWS WINDOWS ON
 THE NORTH/ SOUTH WALLS, THE WALLS ARE INDICATED ON
 SHEET A1-101 TO BE EITHER 5-0 FEET AWAY FROM THE
 PROPERTY LINE OR 5.5 FEET AWAY FROM THE PROPERTY LINE.
 PLEASE PROVIDE THE TOTAL AMOUNT OF SQUARE FEET OF
 WINDOWS AND DOORS AND THE PERCENTAGE OF OPENINGS WITH
 IN THE WALL. AND COMPLIANCE WITH FBC-B TABLE 705.8.
 PLEASE ALSO PROVIDE THE AMOUNT OF OPENINGS AND
 PERCENTAGE OF WALL WITHIN THE EAST WALL AS WELL. PLEASE
 NOTE THE ALLOWABLE AREA FOR FIRE SPRINKLERS CANNOT BE
 TAKEN SENSE THE SPRINKLERS INSTALLED ARE A NFPA 13R.
  
 2C-G) COMPLIED
  
 3-5) COMPLIED.
  
 6) BUILDING # 1. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) FIRE SPRINKLER PLANS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER
 DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH
 INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR
 MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR
 CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA
 STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR
 FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN
 EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
 CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT
 MORE THAN 49 HEADS, NOT WITHSTANDING THE SIZE OF THE
 EXISTING FIRE SPRINKLER SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.