2017-05-05 15:41:46 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17010799 |
| ADD: 539 OGSTON ST. |
| CONT: CANO INC. |
| TEL: |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: FRI. MAY 05/ 2017 |
| ACTION: DENIED |
| |
| 1A) SEMI- COMPLIED. THE COVERSHEET STILL INDICATES |
| BUILDINGS 1 & 3. THE 4300 MILLER PROPERTY WAS |
| SUPPOSEDLY DELETED FROM THIS PORTION OF THE PROJECT ON |
| THE VARIOUS ARCHITECTURAL SHEETS BUILDING 3 IS X-ED |
| THROUGH. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 1B) COMPLIED. THE 4300 MILLER PROPERTY DELETED FROM |
| THIS PORTION OF THE PROJECT. NOTE TO HAVE 2 DIFFERENT |
| OWNERS INVOLVED IN THE PROJECT THE DOCUMENT UNITY OF |
| CONTROL WILL HAVE TO BE DEVELOPED BY THE CITY LAWYERS. |
| |
| 1C) COMPLIED. 308.4 INSTITUTIONAL GROUP I-2. BUILDINGS |
| AND STRUCTURES USED FOR MEDICAL CARE ON A 24-HOUR BASIS |
| FOR MORE THAN FIVE PERSONS WHO ARE INCAPABLE OF |
| SELF-PRESERVATION. THIS GROUP SHALL INCLUDE, BUT NOT BE |
| LIMITED TO, THE FOLLOWING: DETOXIFICATION FACILITIES. |
| ZONING REQUIREMENT: APPLIED FOR A CLASS B USE. |
| |
| 1D)COMPLIED. THE OCCUPANCY I-2 BUILDING TYPE VA. |
| |
| 2) SHEET A-101: |
| 2A) COMPLIED. BUILDING 1- BUILDING CATEGORY II/ 170 |
| MPH/ 3 SECOND GUST/ VULT WIND DESIGN. |
| |
| 2B) 2ND REQUEST. SHEET A-101 SHOWS THAT BOTH TYPES OF |
| FIRE SPRINKLERS NFPA 13 (903.3.1.1) AND NFPA 13R |
| (903.3.1.2). WITH THE BUILDING 3 ELIMINATED FROM THIS |
| PORTION OF THE PROJECT, IT IS ASSUMED THE NFPA 13R |
| (903.3.1.2) WILL BE INSTALLED IN THE GROUP I-2 |
| OCCUPANCY. THIS IS ALLOWED BY 903.2.6 BUT IN DOING SO |
| YOU CANNOT TAKE THE 25% FOR FIRE SPRINKLERS SEE TABLE |
| FBC-B 705.8 FOOTNOTE FOR S (SPRINKLERS) SPRINKLERS HAVE |
| TO COMPLY WITH 903.3.1.1 OR NFPA 13. PLEASE REFIGURE |
| BOTH THE HEIGHT OF WALLS FROM 18 FEET IN HEIGHT AND |
| WINDOW AND DOOR OPENINGS AT 10 % IF 13R SPRINKLERS ARE |
| TO BE INSTALLED. CLARIFY ALSO ON SHEET A-101. |
| 1ST ROUND OF COMMENTS. BUILDING # 1 SHOWS WINDOWS ON |
| THE NORTH/ SOUTH WALLS, THE WALLS ARE INDICATED ON |
| SHEET A1-101 TO BE EITHER 5-0 FEET AWAY FROM THE |
| PROPERTY LINE OR 5.5 FEET AWAY FROM THE PROPERTY LINE. |
| PLEASE PROVIDE THE TOTAL AMOUNT OF SQUARE FEET OF |
| WINDOWS AND DOORS AND THE PERCENTAGE OF OPENINGS WITH |
| IN THE WALL. AND COMPLIANCE WITH FBC-B TABLE 705.8. |
| PLEASE ALSO PROVIDE THE AMOUNT OF OPENINGS AND |
| PERCENTAGE OF WALL WITHIN THE EAST WALL AS WELL. PLEASE |
| NOTE THE ALLOWABLE AREA FOR FIRE SPRINKLERS CANNOT BE |
| TAKEN SENSE THE SPRINKLERS INSTALLED ARE A NFPA 13R. |
| |
| 2C-G) COMPLIED |
| |
| 3-5) COMPLIED. |
| |
| 6) BUILDING # 1. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 7) FIRE SPRINKLER PLANS REQUIRED. W. P. B. |
| ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER |
| DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH |
| INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR |
| MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR |
| CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA |
| STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR |
| FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN |
| EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION |
| CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT |
| MORE THAN 49 HEADS, NOT WITHSTANDING THE SIZE OF THE |
| EXISTING FIRE SPRINKLER SYSTEM. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |