Plan Review Notes
Plan Review Notes For Permit 17010799
Permit Number 17010799
Review Stop P
Sequence Number 1
Notes
Date Text
2017-02-07 16:42:041ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 CODE REQUIREMENTS;
 FLORIDA BUILDING CODE ACCESSIBILITY 2014 5TH EDITION
 FLORIDA BUILDING CODE PLUMBING 2014 5TH EDITION
  
 1. PER THE FLORIDA BUILDING CODE ACCESSIBILITY SEC
 223.2.1 AT LEAST ONE OF THE PATIENT ROOMS SHALL COMPLY
 WITH FBC ACC 805
  
 2. PER FBC ACC 805.4 THE BATHROOM SHALL COMPLY WITH FBC
 ACC 603 THROUGH 610
  
 3. PER FBC ACC 213.2 + 213.3.2 ONE BATHROOM PER SEX FOR
 THE STAFF SHALL COMPLETE WITH FBC ACC 603+604
  
 4. THE SINK IN THE BREAKROOM SHALL COMPLY WITH FBC ACC
 606
  
 5. WILL THE LAUNDRY BE USED EXCLUSIVELY BY THE STAFF IF
 IT IS USED BY PATIENTS OR FAMILY IT SHALL COMPLY WITH
 FBC ACC 611
  
 6.SHT. P-1 + P-5 THE NOTE ON THE GAS SERVICE READS CW
 SERVICE 18 FU PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 7. THE HOT WATER SYSTEM IN BUILDING 1 SHALL HAVE A
 RECIRCULATING SYSTEM PER FBC PL 607.2 HOT OR TEMPERED
 WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 8. A BACKFLOW IS REQUIRED ON THE ICE MACHINE. PER FBC
 PL 608.3
  
 9. THE LAVATORY'S IN THE BATHROOMS USED BY VISITORS
 SHALL HAVE TEMPERED WATER PER FBC PL 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 10. PLEASE PROVIDE MANUFACTURE SPECS FOR THE LENT TRAP.
 PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  