2017-02-07 16:42:04 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| CODE REQUIREMENTS; |
| FLORIDA BUILDING CODE ACCESSIBILITY 2014 5TH EDITION |
| FLORIDA BUILDING CODE PLUMBING 2014 5TH EDITION |
| |
| 1. PER THE FLORIDA BUILDING CODE ACCESSIBILITY SEC |
| 223.2.1 AT LEAST ONE OF THE PATIENT ROOMS SHALL COMPLY |
| WITH FBC ACC 805 |
| |
| 2. PER FBC ACC 805.4 THE BATHROOM SHALL COMPLY WITH FBC |
| ACC 603 THROUGH 610 |
| |
| 3. PER FBC ACC 213.2 + 213.3.2 ONE BATHROOM PER SEX FOR |
| THE STAFF SHALL COMPLETE WITH FBC ACC 603+604 |
| |
| 4. THE SINK IN THE BREAKROOM SHALL COMPLY WITH FBC ACC |
| 606 |
| |
| 5. WILL THE LAUNDRY BE USED EXCLUSIVELY BY THE STAFF IF |
| IT IS USED BY PATIENTS OR FAMILY IT SHALL COMPLY WITH |
| FBC ACC 611 |
| |
| 6.SHT. P-1 + P-5 THE NOTE ON THE GAS SERVICE READS CW |
| SERVICE 18 FU PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 7. THE HOT WATER SYSTEM IN BUILDING 1 SHALL HAVE A |
| RECIRCULATING SYSTEM PER FBC PL 607.2 HOT OR TEMPERED |
| WATER SUPPLY TO FIXTURES. |
| THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| HOT OR TEMPERED WATER. |
| |
| 8. A BACKFLOW IS REQUIRED ON THE ICE MACHINE. PER FBC |
| PL 608.3 |
| |
| 9. THE LAVATORY'S IN THE BATHROOMS USED BY VISITORS |
| SHALL HAVE TEMPERED WATER PER FBC PL 416.5 TEMPERED |
| WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| 10. PLEASE PROVIDE MANUFACTURE SPECS FOR THE LENT TRAP. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |