2017-01-30 16:14:001ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010799
 1/30/17
  
 1) THE ENERGYGAUGE COMPLIANCE SUBMITTALS FOR BUILDINGS
 1 & 3 MUST BE SIGNED AND DATED BY THE OWNER/AGENT- SEE
 PAGE 3 OF THE DOCUMENTS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 SPLIT AND ROOFTOP SYSTEMS.
  
 3) THE O/A CALCULATIONS ARE INCORRECT FOR THE PATIENT
 ROOMS. REFER TO TABLE 403.3: 25 CFM PER PERSON
 REQUIRED.
  
 4) PROVIDE A DETAIL FOR INSTALLATION OF THE CEILING
 DAMPERS IN THE BLDG. #1 CORRIDORS.
  
 5) A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF RTU-1 UNLESS IT CAN BE VERIFIED BY
 MANUFACTURER'S SPECIFICATIONS THAT THE SYSTEM CANNOT
 EXCEED 2000 CFMS OF SUPPLY AIR.
  
 6) SUBMIT SPECS FOR THE WASHER/DRYER UNITS WITH DRYER
 VENTING INSTRUCTIONS FOR MULTIPLE UNITS.
  
 7) PROVIDE STRUCTURAL ENGINEERING FOR: A) INSTALLATION
 OF THE RTU INCLUDING THE ROOF OPENING AND
 REINFORCEMENT, AND THE CURB AND RTU ATTACHMENTS. B)
 INSTALLATION OF THE CU WALL BRACKETS- SECTION 301.15.
  
 8) REFER TO SECTION 401.4 AND PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS FOR THE O/A INTAKE OPENING FOR
 AHU-3.
  
 9) BASED ON THE STRUCTURAL COMMENTS THE OCCUPANCY
 CLASSSIFICATION OF THE BUILDING MAY BE IN QUESTION.
 PLEASE NOTE THAT ADDITIONAL REVIEW COMMENTS MAY OCCUR
 AFTER THIS ISSUE IS RESOLVED AND CORRECTED PLANS ARE
 RESUBMITTED.
  