Plan Review Notes For Permit 17010799 |
Permit Number |
17010799 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-03 15:28:09 | 539 OGSTON STREET | | PERMIT #17010799 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | WWW.KNOXBOX.COM. | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | EXIT SIGNS. | | | | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION | | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES | | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE | | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE | | SPRINKLERS. | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | PRE-ENGINEERED SYSTEMS. | | | | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE | | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | CENTER. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|