Text |
2017-02-14 12:14:21 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, CARD |
| READERS, ETC. A NOTE WILL SUFFICE. |
| 2. PLEASE CORRECT ALL GENERAL NOTES TO COMPLY WITH THE |
| FBC ENERGY CONSERVATION 405 REQUIREMENTS. SECTION 505 |
| HAS BEEN RELOCATED TO 405. PLEASE CORRELATE |
| 3. PROVIDE NOTES TO RISER DIAGRAM INDICATING THE |
| REQUIRED SIGNAGE PER NEC 230.2 MULTIPLE SERVICES. LABEL |
| 1 OF 2 AND 2 OF 2. ALSO LABEL MAINS 1 OF 4 ETC. PER NEC |
| 230.70 |
| 4. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD |
| MARKINGS; MODIFICATIONS; SEE VERBIAGE IN CODE. |
| 5. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15 |
| AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED |
| WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER |
| CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW |
| COMPLIANCE ACCORDINGLY. |
| 6. PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC EC |
| 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES |
| PER CODE SECTION. |
| 7. PROVIDE A NOTE TO POWER PLAN TO INDICATE |
| REQUIREMENTS OF NEC 513.17A- REDUNDANT GROUNDING FOR |
| ALL OUTLETS WITHIN THE PATIENT VICINITY; SEE VERBIAGE |
| IN THE CODE. |
| 8. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL |
| COMMENTS RELATED TO ELECTRICAL. |
| 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| THIS PROJECT. |
| |
| |