2017-02-13 13:23:58 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17010799 |
| ADD: 539 OGSTON ST. |
| CONT: CANO INC. |
| TEL: |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. FEB. 10/ 2017 |
| ACTION: DENIED |
| |
| 1A) PLEASE SUBMIT A SURVEY OF THE PROPERTY. BUILDING # |
| 3 IS ON THE PROPERTY ADDRESSED 539 OGSTON ST. PCN |
| 7443-44-03-01-000-7470 AND BUILDING # 1 IS ON THE |
| PROPERTY ADDRESSED 4300 MILLER AVE. PCN |
| 74-43-44-03-01-000-7450 AND A DIFFERENT OWNER? LOTS |
| OWNED BY DIFFERENT OWNERS CANNOT OBTAIN A UNITY OF |
| TITLE. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: BUILDING. |
| SURVEY OF PROPERTY. |
| |
| 1B) TWO PERMITS MAY BE REQUIRED SINCE THERE IS WORK |
| BEING COMPLETED ON 2 DIFFERENT PROPERTIES WITH TWO |
| DIFFERENT OWNERS. FOR THE (2) PERMITS, PLEASE SPLIT THE |
| DOLLAR AMOUNT SHOWN ON 539 OGSTON ST. PERMIT |
| ACCORDINGLY TO REFLECT THE NEW DOLLAR AMOUNT OF WORK |
| PROPOSED FOR EACH PROPERTY. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| TO RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE |
| COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA |
| STATUTES. |
| |
| 1C) THE COVERSHEET INDICATES THIS FACILITY TO BE A |
| DETOX CENTER PLEASE REVIEW SHEET A1.101 LIST THIS |
| OCCUPANCY TYPE TO BE A R4. A R4 IS FOR ALCOHOL AND DRUG |
| CENTERS (FBC-B 310.4, MORE THAN FIVE BUT NOT MORE THAN |
| 16 PERSONS, EXCLUDING STAFF, WHO RESIDE ON A 24-HOUR |
| BASIS IN A SUPERVISED RESIDENTIAL ENVIRONMENT AND |
| RECEIVE CUSTODIAL CARE). |
| 308.4 INSTITUTIONAL GROUP I-2. BUILDINGS AND STRUCTURES |
| USED FOR MEDICAL CARE ON A 24-HOUR BASIS FOR MORE THAN |
| FIVE PERSONS WHO ARE INCAPABLE OF SELF PRESERVATION. |
| THIS GROUP SHALL INCLUDE, BUT NOT BE LIMITED TO, THE |
| FOLLOWING:DETOXIFICATION FACILITIES. ZONING |
| REQUIREMENT: APPLIED FOR A CLASS B USE. |
| |
| 1D) SHEET A1.101 ALSO LIST THIS BUILDING TYPE AS A VB. |
| PLEASE REVIEW FBC-B TABLE 503, I2 OCCUPANCIES CANNOT BE |
| CONSTRUCTED AS AN TYPE VB CONSTRUCTION. |
| |
| 2) SHEET A-101: |
| 2A) BUILDINGS 1 & 3 IS SHOWN TO HAVE A 170 MPH/ 3 |
| SECOND GUST/ VULT WIND DESIGN. UNDER THE SAME HEADING |
| THE BUILDING RISK CATEGORY (FBC-B TABLE 1604.5) LIST |
| BOTH OF THESE BUILDINGS AS A RISK CATEGORY III. |
| PLEASE REVIEW THE TABLE 1604.5, THESE BUILDINGS ARE |
| BOTH A RISK CATEGORY II STRUCTURES LISTED AT 170 MPH/ |
| 3SECOND GUST/ VULT. |
| |
| 2B) BUILDING # 1 SHOWS WINDOWS ON THE NORTH/ SOUTH |
| WALLS, THE WALLS ARE INDICATED ON SHEET A1-101 TO BE |
| EITHER 5-0 FEET AWAY FROM THE PROPERTY LINE OR 5.5 FEET |
| AWAY FROM THE PROPERTY LINE. PLEASE PROVIDE THE TOTAL |
| AMOUNT OF SQUARE FEET OF WINDOWS AND DOORS AND THE |
| PERCENTAGE OF OPENINGS WITH IN THE WALL. AND COMPLIANCE |
| WITH FBC-B TABLE 705.8. PLEASE ALSO PROVIDE THE AMOUNT |
| OF OPENINGS AND PERCENTAGE OF WALL WITHIN THE EAST WALL |
| AS WELL. PLEASE NOTE THE ALLOWABLE AREA FOR FIRE |
| SPRINKLERS CANNOT BE TAKEN SENSE THE SPRINKLERS |
| INSTALLED ARE A NFPA 13R. |
| |
| 2C) PLEASE ALSO PROVIDE THE OPENING SIZES OF THE |
| WINDOWS IN THE SLEEPING ROOMS AND COMPLIANCE WITH 2014 |
| FBC-B 1029.2 MINIMUM SIZE. PROVIDE THE OVERALL SIZE OF |
| THE WINDOW, TYPE OF WINDOW AND THE ACTUAL VENT SIZE AND |
| COMPLIANCE. |
| |
| 2D) UNDER SECTION FBC-B 407.4.3.5.3 TRAVEL DISTANCE. |
| THE TRAVEL DISTANCE BETWEEN ANY POINT IN A CARE SUITE |
| CONTAINING SLEEPING ROOMS AND AN EXIT ACCESS DOOR FROM |
| THAT CARE SUITE SHALL BE NOT GREATER THAN 100 FEET (30 |
| 480 MM). |
| |
| 2E) PLEASE SHOW COMPLIANCE WITH: FBC-B 407.4.1.1 |
| LOCKING DEVICES. LOCKING DEVICES THAT RESTRICT ACCESS |
| TO A CARE RECIPIENT?S ROOM FROM THE CORRIDOR AND THAT |
| ARE OPERABLE ONLY BY STAFF FROM THE CORRIDOR SIDE SHALL |
| NOT RESTRICT THE MEANS OF EGRESS FROM THE CARE |
| RECIPIENT?S ROOM. |
| EXCEPTIONS: |
| 1. THIS SECTION SHALL NOT APPLY TO ROOMS IN PSYCHIATRIC |
| TREATMENT AND SIMILAR CARE AREAS. |
| 2. LOCKING ARRANGEMENTS IN ACCORDANCE WITH SECTION |
| 1008.1.9.6. |
| |
| 2F) PLEASE EXPLAIN WHAT THE PATIENT OVERFLOW ROOM IS TO |
| BE USED FOR? ADDITIONAL INFORMATION IS REQUIRED. |
| 107.2.1.3. |
| |
| 2G) PLEASE PROVIDE COMPLIANCE WITH : FBC-B 906.1 WHERE |
| REQUIRED. PORTABLE FIRE EXTINGUISHERS SHALL BE |
| INSTALLED IN THE FOLLOWING LOCATIONS. 1. IN GROUP A, B, |
| E, F, H, I, M, R-1, R-2, R-4 AND S OCCUPANCIES. (5) |
| 5. WHERE REQUIRED BY THE FLORIDA FIRE PREVENTION CODE. |
| |
| 2G) 407.7 FIRE ALARM SYSTEM. A FIRE ALARM SYSTEM SHALL |
| BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.6. |
| 3) SHEET A1.101 BUILDING # 1 SHOW COMPLIANCE WITH: 2014 |
| FBC-ACCESSIBILITY CODE. 223.2 HOSPITALS, REHABILITATION |
| FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION |
| FACILITIES. HOSPITALS, REHABILITATION FACILITIES, |
| PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES |
| SHALL COMPLY WITH 223.2. |
| 223.2.1 FACILITIES NOT SPECIALIZING IN TREATING |
| CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES NOT |
| SPECIALIZING IN TREATING CONDITIONS THAT AFFECT |
| MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE, |
| OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY |
| FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT |
| BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS |
| PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. |
| |
| 3A) ACCESS. CODE. 805.1 GENERAL. MEDICAL CARE FACILITY |
| AND LONG-TERM CARE FACILITY PATIENT OR RESIDENT |
| SLEEPING ROOMS REQUIRED TO PROVIDE MOBILITY FEATURES |
| SHALL COMPLY WITH 805. |
| |
| 3B) ACCESS. CODE 805.3 CLEAR FLOOR OR GROUND SPACE. |
| |
| 3C) ACCESS. CODE 805.4 TOILET AND BATHING ROOMS. TOILET |
| AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A |
| PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH |
| 603. WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET, |
| ONE LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY |
| WITH THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610. |
| PLEASE DESIGNATE WHICH RESTROOM WILL MEET THESE |
| REQUIREMENTS. |
| |
| 4) ENERGY CODE: |
| 4A) BUILDING # 1 THE PROJECT SUMMARY INDICATES THE |
| CONDITIONED AREA IS 4071 SQ. FT. WHEREAS THE EXTERIOR |
| MEASUREMENTS OF 56 X 69= 3869 SQ. FT.? PLEASE REVIEW |
| THE AIR CONDITIONED SQUARE FOOTAGE OF THE BUILDING. |
| ADDITIONAL INFORMATION REQUIRED. 107.2.1.3. |
| |
| 4B) BUILDING # 1 THE PROJECT SUMMARY LIST THIS AS AN |
| OFFICE WHEREAS THIS IS A MIXED USE BUILDING BUT THE |
| MAIN USE IS A R4 OCCUPANCY. ADDITIONAL INFORMATION IS |
| REQUIRED. 107.2.1.3. |
| |
| 4C) PLEASE REVIEW SHEET A -501 WALL TYPE 1 THE EXTERIOR |
| WALL INSULATION FOR BOTH BUILDING 1 & 3. THE WALL |
| INSULATION SHOULD GO FROM THE ROOF TRUSS LINE TO THE |
| FLOOR, THAT?S NOT IS IN THE WALL DESCRIPTION. |
| FBC-ENERGY CODE 402.2.2. |
| |
| 4D) PLEASE PROVIDE A DETAIL IN THE PLANS WHERE |
| COMPLIANCE WITH THE ROOF INSULATION WILL BE PLACED. THE |
| ENERGY GAGE SUMMIT DATA LIST THE EXTERIOR WALLS TO BE |
| 16 FEET TALL. ENERGY C402.2.3. |
| |
| 5) PLEASE SHOW WHERE COMPLIANCE WITH 2014 FBC-ACCESS. |
| CODE 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 6) BUILDING # 1. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| BUILDING # 3/ OFFICE. |
| |
| 7) A SEPARATE PERMIT APPLICATION 3 WILL BE REQUIRED FOR |
| 4300 MILLER AVE./ BUILDING # SINCE THE PALM BEACH |
| COUNTY PROPERTY APPRAISERS OFFICE INDICATES DIFFERENT |
| OWNERS THAN 539 OGSTON ST. 105.1 PERMITS REQUIRED. |
| |
| 8) BUILDINGS 1 & 3 IS SHOWN TO HAVE A 170 MPH/ 3 SECOND |
| GUST/ VULT WIND DESIGN. UNDER THE SAME HEADING THE |
| BUILDING RISK CATEGORY (FBC-B TABLE 1604.5) LIST BOTH |
| OF THESE BUILDINGS AS A RISK CATEGORY III. |
| PLEASE REVIEW THE TABLE 1604.5, THESE BUILDINGS ARE |
| BOTH A RISK CATEGORY II STRUCTURES LISTED AT 170 MPH/ |
| 3SECOND GUST/ VULT. |
| |
| 9) BUILDING # 3 COMPLIANCE WITH 2014 FBC-ACCESS. CODE |
| 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO |
| PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED |
| AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL |
| ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE |
| ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY |
| BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS |
| ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS |
| ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS |
| INSTALLING GRAB BARS, ENLARGING TOILET STALLS, |
| INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET |
| CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING |
| ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE |
| TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION |
| DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV) |
| COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE |
| DRINKING FOUNTAIN. |
| |
| 10) BUILDING # 3 IS SHOWN RIGHT ON THE PROPERTY LINE: |
| 10A) PLEASE SEE TABLE 705.8 NO OPENINGS ARE PERMITTED |
| UP TO 3 FEET FROM THE PROPERTY LINE. IT APPEARS THE |
| LAUNDRY ROOM DOOR AND WAITING ROOM WINDOW ARE WITHIN |
| THE 3 FEET OF THE PROPERTY LINE. |
| |
| 10B) THE SHEET A-101 SHOWS THE SOUTH WALL OF BUILDING # |
| 3 RIGHT ON THE PROPERTY LINE, PLEASE PROVIDE HOW |
| COMPLIANCE WITH FBC-B 705.2 PROJECTIONS. CORNICES, EAVE |
| OVERHANGS, EXTERIOR BALCONIES AND SIMILAR PROJECTIONS |
| EXTENDING BEYOND THE EXTERIOR WALL SHALL CONFORM TO THE |
| REQUIREMENTS OF THIS SECTION AND SECTION 1406. EXTERIOR |
| EGRESS BALCONIES AND EXTERIOR EXIT STAIRWAYS AND RAMPS |
| SHALL ALSO COMPLY WITH SECTIONS 1019 AND 1026, |
| RESPECTIVELY. PROJECTIONS SHALL NOT EXTEND ANY CLOSER |
| TO THE LINE USED TO DETERMINE THE FIRE SEPARATION |
| DISTANCE THAN SHOWN IN TABLE 705.2. |
| |
| FBC-B 705.2.3 COMBUSTIBLE PROJECTIONS. COMBUSTIBLE |
| PROJECTIONS EXTENDING TO WITHIN 5 FEET (1524 MM) OF THE |
| LINE USED TO DETERMINE THE FIRE SEPARATION DISTANCE, OR |
| LOCATED WHERE OPENINGS ARE NOT PERMITTED, OR WHERE |
| PROTECTION OF SOME OPENINGS IS REQUIRED SHALL BE OF AT |
| LEAST 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION, TYPE |
| IV CONSTRUCTION, FIRE-RETARDANT-TREATED WOOD OR AS |
| REQUIRED BY SECTION 1406.3. |
| |
| 11) SHEET A-103 SHOWS (3) STACKED WASHER AND DRYERS. |
| PLEASE SHOW COMPLIANCE WITH THE 2014 ACCESS. CODE: |
| 309.2 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL |
| BE PROVIDED. |
| |
| 309.3 HEIGHT. |
| OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF |
| THE REACH RANGES SPECIFIED IN 308. |
| |
| 309.4 OPERATION. |
| OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND |
| SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING |
| OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE |
| PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM. |
| |
| 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |