2017-04-24 14:59:47 | 2ND REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. YOUR RESPONSE TO PREVIOUS COMMENT #6 STATES THERE IS |
| NO GARBAGE DISPOSAL USED BUT ON P-1 ON THE PLUMBING |
| FIXTURE SCHEDULE P-4 LIST A GARBAGE DISPOSAL. PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| PREVIOUS COMMENT 6. IF YOUR USING A GARBAGE DISPOSAL ON |
| P-4 IT SHALL COMPLY WITH FBC PL 1003.3.2 FOOD WASTE |
| GRINDERS. |
| WHERE FOOD WASTE GRINDERS CONNECT TO GREASE |
| INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE |
| DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR. |
| SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE |
| SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE |
| GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA |
| SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER. |
| |
| 2. PROVIDE THE SIZE OF EXISTING GREASE TRAP YOU |
| PROVIDED SIZING CALCULATIONS BUT I NEED TO KNOW THE |
| SIZE OF THE EXTSITING TRAP TO VERIFY THAT IT IS LARGE |
| ENOUGH . PER FBC PL 1003.3.4.1 |
| |
| PREVIOUS COMMENT 10. THE EXISTING GREASE TRAP SHALL BE |
| INSPECTED AND VERIFIED TO BE STRUCTURALLY SOUND AND IN |
| GOOD WORKING ORDER BY A SIGNED AND SEALED LETTER FROM |
| THE ENGINEER. PER WPB AMEND TO FBC 107.2.1 |
| I AGREE THAT THE INSPECTION AND CERTIFICATION IS NOT |
| REQUIRED TO BE DONE BY AN ENGINEER, PLEASE INDICATE ON |
| THE PLAN THAT AN INSPECTION SHALL BE COMPLETED AND |
| CERTIFIED BY UTILITIES PRIOR TO FINAL PLUMBING |
| INSPECTION, THE OWNER CAN CONNTACT JEFF ODOMS AT |
| 822-2172 OR [email protected] TO SCHEDULE AN INPECTION |
| WITH UTILITIES. |
| |
| |
| |
| DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |