Plan Review Notes For Permit 17010775 |
Permit Number |
17010775 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-01 10:34:02 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010775 | | 2/1/17 | | | | 1) SHEET M-1: PROVIDE EQUIPMENT SCHEDULES FOR EF-1 & 2. | | | | 2) M-1: SOME OF THE REQUIRED DATA IS MISSING FROM THE | | HEAT LOAD SUMMARY- SEE SECTION C403.2.1 EXCEPTION | | FBC-14 ENERGY CONSERVATION AND PROVIDE THE AREA IN | | SQUARE FEET, GRAINS WATER (DIFFERENCE), RELATIVE | | HUMIDITY, AND TOTAL LATENT GAIN. | | | | 3) M-1: AHU-2 REQUIRES HEAT PER THE CALCULATIONS AND | | SECTION 309.1. | | | | 4) M-2: THE DUCT LAYOUT FOR AHU-1 DOES NOT SHOW SUPPLY | | AND RETURN CFMS AT EACH DIFFUSER AND GRILL LOCATION. | | | | 5) M-2: BASED ON THE DRAWING, IT DOES NOT APPEAR THAT | | THE REQUIRED CFMS OF O/A WILL BE PROVIDED TO THE DINING | | ROOM AREA. | | | | 6) M-2: PROVIDE STRUCTURAL ENGINEERING FOR INSTALLATION | | OF THE NEW CONDENSER RACK AND MOUNTING OF THE UNIT TO | | THE RACK- SECTION 301.15. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|