2017-02-01 10:34:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010775
 2/1/17
  
 1) SHEET M-1: PROVIDE EQUIPMENT SCHEDULES FOR EF-1 & 2.
  
 2) M-1: SOME OF THE REQUIRED DATA IS MISSING FROM THE
 HEAT LOAD SUMMARY- SEE SECTION C403.2.1 EXCEPTION
 FBC-14 ENERGY CONSERVATION AND PROVIDE THE AREA IN
 SQUARE FEET, GRAINS WATER (DIFFERENCE), RELATIVE
 HUMIDITY, AND TOTAL LATENT GAIN.
  
 3) M-1: AHU-2 REQUIRES HEAT PER THE CALCULATIONS AND
 SECTION 309.1.
  
 4) M-2: THE DUCT LAYOUT FOR AHU-1 DOES NOT SHOW SUPPLY
 AND RETURN CFMS AT EACH DIFFUSER AND GRILL LOCATION.
  
 5) M-2: BASED ON THE DRAWING, IT DOES NOT APPEAR THAT
 THE REQUIRED CFMS OF O/A WILL BE PROVIDED TO THE DINING
 ROOM AREA.
  
 6) M-2: PROVIDE STRUCTURAL ENGINEERING FOR INSTALLATION
 OF THE NEW CONDENSER RACK AND MOUNTING OF THE UNIT TO
 THE RACK- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER