2017-04-24 16:27:09 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. PROVIDE SIZE OF EXISTING PIPING FROM METER TO NEW |
| BRANCH PIPING TO WATER HEATER IN ORDER TO INSURE THAT |
| THERE IS AN ADEQUATE SUPPLY OF GAS FOR THE SYSTEM. PER |
| FBC FG 402.1 |
| |
| 2. THE NOTE ABOVE GAS RISER REFERENCES 2010 FBC FUEL |
| GAS WE ARE UNDER 2014 5TH EDITION PLEASE CLARIFY. PER |
| WPB AMEND TO FBC |
| |
| 3. NUMBER 6 ON THE RISER IS SHOWN ON THE BRANCH FOR THE |
| HEATER IF THIS IS THE EXISTING MANUAL RESET SOLENOID |
| VALVE FOR INTERLOCKED WITH THE FIRE SUPPRESSION SYSTEM |
| IT SHALL BE SHOWN ON THE EXISTING BRANCH TO RANGE. PER |
| WPB AMEND TO FBC |
| |
| 4. THE SEDIMENT TRAP SHALL NOT BE INSTALL ON HE |
| HORIZONTAL RUN LIKE IT IS SHOWN ON THE RISER IT SHALL |
| COMPLY WITH FBC FG 408.4 SEDIMENT TRAP. |
| WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF |
| THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED |
| DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO |
| THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT |
| TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED |
| NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE |
| BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE |
| 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT |
| TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS, |
| DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED |
| FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT |
| BE SO EQUIPPED. |
| |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2014 FUEL GAS CODE SEC. 304. |
| |
| 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| SEC. 502 THRU 505. |
| |
| 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| |
| |
| |
| |
| |
| |
| |
| |
| FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT |
| THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL |
| COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |