2017-02-03 07:49:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE
 AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PLEASE ADDRESS MECHANICAL COMMENTS REGARDING E/FANS
 3. CLARIFY PANEL SCHEDULE PANEL2 SHOWN AS A SINGLE
 PHASE BUT RISER INDICATES A 3PHASE PANEL. FBC 107.3.5
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  