Notes
Date Text
2017-02-13 10:04:49APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. PROVIDE A NEW ONE-LINE RISER DIAGRAM REFLECTING NEW
 150AMP SERVICE
 3. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 4. LABEL RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET.
  
 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  