Plan Review Notes
Plan Review Notes For Permit 17010676
Permit Number 17010676
Review Stop M
Sequence Number 1
Notes
Date Text
2017-02-14 13:43:131ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010676
 2/14/17
  
 1) THE LICENSING SCOPE FOR BOTH A GENERAL CONTRACTOR
 AND A UNDERGROUND UTILITIES CONTRACTOR DOES NOT INCLUDE
 INSTALLATION OF PIPING THAT IS AN INTEGRAL PART OF A
 FIRE PROTECTION SYSTEM BEGINNING AT A POINT WHERE THE
 PIPING IS USED EXCLUSIVELY FOR SUCH SYSTEM- PLEASE SEE
 FL. STATUTES 489.113(2)(D), 489.105(3)(N), AND 633.102.
  
 2) SHEET C5.02: THE PLAN APPEARS INCOMPLETE FOR THE
 SCOPE OF WORK. PLEASE SHOW THE UNDERGROUND FIRE LINE
 RUN BEGINNING AT THE POINT OF CONNECTION TO THE MAIN
 WATER LINE TO THE BUILDING. PLEASE SHOW THE LOCATION OF
 THE REQUIRED BACK FLOW PREVENTER, AND PROVIDE PIPING
 DETAILS AND SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  