2017-05-18 18:41:32RESIDENTIAL (R3) ADDITIONS/ALTERATIONS SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE:
 OLD PLANS WERE NOT RESUBMITTED AS REQUESTED ON PREVIOUS
 CHECKLIST. THIS DELAYS THE REVIEW PROCESS AND PROVIDES
 NO REFERENCE OF WHAT WAS REVIEWED THE FIRST TIME.
  
  
 ORIGINAL COMMENT:
 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS SUBMITTAL.
 PROVIDE A PERMIT APPLICATION FOR EACH BUILDING. MAIN
 HOUSE AND GUEST HOUSE. SEC. 105.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. NEED A
 PERMIT APPLICATION FOR EACH STRUCTURE.
  
 2- GUEST HOUSE ORIGINAL COMMENT:
 NEED TO SPECIFY 1 HOUR FIRE RATED ASSEMBLY FOR THE WEST
 WALL WITH FIRE EXPOSURE FROM BOTH SIDES AS REQUIRED BY
 TABLE R302.1(1). ASSEMBLY NEED TO TESTED IN ACCORDANCE
 WITH ASTM E 119 OR UL 263.
 RESPONSE: NEED 1 HOUR FIRE RATED WALL ASSEMBLY THAT
 PROVIDES FIRE PROTECTION FROM BOTH SIDES. THAT'S WHY I
 WROTE BOTH SIDES IN CAPITAL LETTERS TO MAKE SURE PROPER
 ASSEMBLY WAS SPECIFIED. THE SPECIFIED ASSEMBLY DESIGN
 NO. U356 IS FOR FIRE EXPOSURE ON THE INTERIOR FACE
 ONLY. REVISE AS REQUIRED. SPECIFY ASSEMBLY THAT
 PROVIDES PROTECTION ON BOTH SIDES. NOTE: THE 1 HOUR
 PROTECTION FROM BOTH SIDES APPLIES TO FIRST AND SECOND
 FLOOR NOT JUST THE SECOND FLOOR ADDITION. REVISE PLANS
 SHOWING COMPLIANCE FOR FIRST AND SECOND FLOOR.
  
 3- GUEST HOUSE ORIGINAL COMMENT:
 GUEST BEDROOM WINDOW ABOVE GARAGE DOESN'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL
 5TH EDITION (2014). NEED TO COMPLY WITH THE MIN. CLEAR
 HEIGHT AND TOTAL CLEAR OPENING. REVISE AS REQUIRED.
 RESPONSE: NONE OF THE WINDOWS ON THE SECOND FLOOR
 BEDROOM COMPLIES WITH THE EGRESS REQUIREMENTS. SINGLE
 HUNG PRODUCT APPROVAL SUBMITTED IS FOR CGI WINDOWS.
 LOOK ON THE INTERNET FOR THE WINDOW SIZE CHART FOR
 SIZES THAT COMPLY FOR EGRESS (SECOND FLOOR) AND REVISE
 SIZE AS REQUIRED.
  
 4- ORIGINAL COMMENT: BUILDING SECTION AT MAIN HOUSE
 2/A2.1 SHOWS A STAIRWAY WITH OPEN RISERS. OPEN RISERS
 ARE NOT ALLOWED UNLESS THEY COMPLY WITH SEC. R311.7.5.1
 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE.
 RESPONSE: SECTION 2/A2.1 AND SECTION NEEDS TO BE
 REVISED/CLARIFIED. (1)THE HEADROOM CLEARANCE OF 6'-8"
 AS SHOWN WITH DASHED LINES DOESN'T WORK. (2)SPACING
 BETWEEN PICKETS CAN NOT BE 4" MIN. IT HAS TO BE LESS
 THAN 4" SO AN SPHERE CAN NOT PASS THRU. (3)MATERIALS
 AND DIMENSIONS FOR THE CONSTRUCTION OF STAIRS IS NOT
 SPECIFIED. UNABLE TO VERIFY THE SPACE BETWEEN OPEN
 RISERS FOR COMPLIANCE WITH THE OPEN RISERS EXCEPTION.
 REVISE DETAILS AND SPECIFICATIONS AS REQUIRED. NOTE:
 STAIRS/HANDRAILS SHOP DRAWINGS WILL BE REQUIRED FOR
 REVIEW PRIOR TO CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
 ARCHITECT TO REVIEW AND APPROVE PRIOR TO SUBMITTAL.
  
 5- ORIGINAL COMMENT: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL STAIRS,
 HANDRAILS AND GUARDRAILS (INCLUDING BALCONY GUARDRAILS)
 SHOWING COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5
 AND ALL THE REQUIREMENTS OF SEC. R311.7.5, SEC.
 R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 RESPONSE: ARCHITECT TO SPECIFY THE LIVE LOADS DESIGN
 CRITERIA REQUIRED BY TABLE R301.5 SO SHOP DRAWINGS ARE
 PRODUCED BASED ON THAT DESIGN CRITERIA. DRAWINGS
 SUBMITTED DON'T PROVIDE THIS INFORMATION.
  
 6- ORIGINAL COMMENT: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE NEW SCREEN
 ENCLOSURE IN THE OPEN LOGGIA. SPECIFY ALL FRAMING
 MEMBERS AND FASTENERS AND PROVIDE MESH SPECIFICATIONS.
 SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: ARCHITECT STATED ON PLANS TO PROVIDE SIGNED
 AND SEALED SHOP DRAWINGS FOR THE SCREEN ENCLOSURE.
 THERE IS NO SHOP DRAWINGS SUBMITTAL FOR SCREEN
 ENCLOSURES. ARCHITECT NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE SCREEN
 ENCLOSURE OR NEED TO PROVIDE COMPLETE ENGINEERED
 DRAWINGS AND SPECIFICATIONS UNDER A SEPARATE PERMIT.
  
 7- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R16
 SUBMITTED;
 A) ORIGINAL COMMENT: CLEARLY SPECIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ORIGINAL COMMENT: IF SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED TO MEET
 THE DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 SEE NOTE #8 ON PAGE 2 OF 58 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ORIGINAL COMMENT: BALCONY DECK UNDERLAYMENT. NOTE:
 NEED PRODUCT APPROVAL THAT IS DESIGNED TO BE USED WITH
 THE SPECIFIC DECK FINISH MATERIAL TO BE INSTALLED IN
 THIS HOUSE. IN ADDITION CLEARLY IDENTIFY SPECIFIC
 ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF DECK ZONES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ORIGINAL COMMENT: ROOF CLAY TILE. NOA 12-0210.01
 SUBMITTED EXPIRED ON 02/01/16. NEED TO PROVIDE CURRENT
 PRODUCT APPROVAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) ORIGINAL COMMENT: ROOF TILE ADHESIVE IF SPECIFIED BY
 THE ARCHITECT OF RECORD. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) ORIGINAL COMMENT: OVERHEAD GARAGE DOOR THAT MEETS
 THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT OF
 RECORD ON SHEET A3.2.
 NOA 16-0617.07 SUBMITTED DOESN'T MEET THOSE DESIGN
 PRESSURES.
 RESPONSE: IT LOOKS LIKE THE DESIGN PRESSURES SHOWN ON
 SHEET A3.2 WERE REVISED. THE REVISED DESIGN PRESSURES
 DON'T SEEM TO COMPLY WITH THE DESIGN PRESSURES FOR A
 TWO STORY STRUCTURE LOCATED IN EXPOSURE "D". REVISE
 DESIGN PRESSURES AS REQUIRED OR PROVIDE COMPLETE
 CALCULATIONS SHOWING HOW THE SPECIFIED DESIGN PRESSURES
 WERE OBTAINED.
  
 E) ORIGINAL COMMENT: SINGLE HUNG WINDOWS. NEED LARGE
 MISSILE IMPACT RESISTANT PRODUCT APPROVAL. NOA
 15-0512.08 SUBMITTED IS FOR SMALL MISSILE IMPACT
 RESISTANT.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 F) ORIGINAL COMMENT: WINDOW MULLIONS AS SHOWN ON PLANS.
 AND, SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 G) ORIGINAL COMMENT: FIXED WINDOWS AS SPECIFIED ON
 PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 H) ORIGINAL COMMENT: GUEST HOUSE EXTERIOR SWING DOOR AS
 SHOWN ON PLANS.
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 10- ORIGINAL COMMENT: PROVIDE DETAILS AND
 SPECIFICATIONS FOR THE GARAGE AND DWELLING SEPARATION
 AS REQUIRED BY TABLE R302.6 FBC-RESIDENTIAL.
 RESPONSE: SHEET A1.3 DOESN'T PROVIDE INFORMATION FOR
 THE GARAGE AND DWELLING SEPARATION. THE UL FIRE
 SEPARATION MENTIONED BY THE ARCHITECT ON THE RESPONSE
 LETTER IS FOR THE REQUIRED FIRE RATED EXTERIOR WALL NOT
 FOR THE SEPARATION REQUIRED AT THE GARAGE CEILING.
 PROVIDE COMPLETE INFORMATION.
  
 PLEASE READ THE FOLLOWING:
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  