Plan Review Notes
Plan Review Notes For Permit 17010618
Permit Number 17010618
Review Stop P
Sequence Number 1
Notes
Date Text
2017-02-09 12:34:321ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P2 RISER DIAGRAM HAS THE FOLLOWING DEFICIENCY.
 A) THE WASHING MACHINE IS NOT VENTED.
 B) BATHROOM #2 IS NOT VENTED.
 C) THE SHOWER AND WATER CLOSET IN BATHROOM #1 IS NOT
 VENTED.
 D) THE LAVATORY IN BATHROOM #1 IS NOT VENTED.
 E) THE KITCHEN IS NOT VENTED.
 PER FBC RES P3101.2.1
  
 2. CLEAN OUTS ARE REQUIRED AT THE BASE OF ALL SOIL AND
 WASTE STACKS. PER FBC RES P3005.2.6
  
 3. THE WET BAR ABOVE THE GARAGE SHALL CONNECT TO THE
 BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER
 FBC RES P3108.1
  
 4. SHOW THE LOCATION OF THE WATER HEATER INDICATE IF
 NEW OR EXISTING. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  