Plan Review Notes
Plan Review Notes For Permit 17010618
Permit Number 17010618
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-06 13:15:56PLAN DENIED
 1) PROVIDE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 ON THE FIRE PLACE IF NOT EXISTING. 304.1 FBC (M) 2014
 2) A/C #1 PROVIDE DUCT SIZE ON RETURN AIR FROM
 AIR HANDLER TO 24 X18 CAN. 107 FBC 2014
 3) A/C # 1 14 SUPPLY DUCT FROM 2ND FLOOR TO 1ST FL
 IS TIED INTO WHAT SIZE DUCT SECTION 107 FBC 2014
  