| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. |
| |
| PLAN SHEET E2: |
| |
| ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH |
| CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12 |
| |
| GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE REAR |
| ELEVATION. NEC 210.8 |
| |
| CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE |
| LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9 |
| |
| HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES |
| NEED TO BE RATED FOR INSULATION CONTACT (IC). NEC |
| 410.116; FBC R 4004 |
| |
| A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR |
| MORE IN WIDTH (KITCHEN). NEC 210.52(A)(2) |
| |
| ACCESS TO THE OUTSIDE AIR CONDITION UNIT DISCONNECTS |
| MAY NOT BE BLOCKED BY THE UNITS. NEC 110.26 |
| |
| A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC |
| 210.52 (F), FBC R 3703.3 |
| |
| REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| |
| A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED |
| LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING |
| FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC |
| ER404.1 |
| |
| PLAN SHEET E3: |
| |
| A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR |
| MORE IN WIDTH (GUEST HOUSE). NEC 210.52(A)(2) |
| |
| A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC |
| 210.52 (F), FBC R 3703.3 |
| |
| |
| AHU #3 REQUIRES AN EQUIPMENT DISCONNECT. NEC 422.30 FBC |
| R E4101.5 |
| |
| AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94; FBC R E3609 |
| |
| PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR GUEST |
| HOUSE PANEL B. NEC 250.32 |
| |
| VERIFY THAT PANEL B HAS THE REQUIRED SAFETY CLEARANCES |
| AND IS RATED FOR A WET LOCATION. NEC 110.26, 110.11 |
| |
| |