Plan Review Notes
Plan Review Notes For Permit 17010618
Permit Number 17010618
Review Stop E
Sequence Number 1
Notes
Date Text
2017-01-26 14:45:28 
 17010618
 200 GREENWOOD DRIVE
 RESIDENTIAL REMODEL/ADDITION
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PLAN SHEET E2:
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE REAR
 ELEVATION. NEC 210.8
  
 CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE
 LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT (IC). NEC
 410.116; FBC R 4004
  
 A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR
 MORE IN WIDTH (KITCHEN). NEC 210.52(A)(2)
  
 ACCESS TO THE OUTSIDE AIR CONDITION UNIT DISCONNECTS
 MAY NOT BE BLOCKED BY THE UNITS. NEC 110.26
  
 A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC
 210.52 (F), FBC R 3703.3
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC
 ER404.1
  
 PLAN SHEET E3:
  
 A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR
 MORE IN WIDTH (GUEST HOUSE). NEC 210.52(A)(2)
  
 A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC
 210.52 (F), FBC R 3703.3
  
  
 AHU #3 REQUIRES AN EQUIPMENT DISCONNECT. NEC 422.30 FBC
 R E4101.5
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR GUEST
 HOUSE PANEL B. NEC 250.32
  
 VERIFY THAT PANEL B HAS THE REQUIRED SAFETY CLEARANCES
 AND IS RATED FOR A WET LOCATION. NEC 110.26, 110.11
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  