2017-03-01 15:03:57RESIDENTIAL (R3) ADDITIONS/ALTERATIONS BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS SUBMITTAL.
 PROVIDE A PERMIT APPLICATION FOR EACH BUILDING. MAIN
 HOUSE AND GUEST HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- GUEST HOUSE:
 A) ACCORDING TO SURVEY SUBMITTED, THE GARAGE SEPARATION
 ON THE WEST SIDE IS 2.0 FEET TO THE PROPERTY LINE.
 TABLE R302.1(1) FBC-RESIDENTIAL DOESN'T ALLOW OPENINGS.
 REVISE ALL WINDOW OPENINGS AND THE PROPOSED OPENING ON
 THE WEST SIDE UNDERNEATH THE NEW STAIRWAY.
  
 B) NEED TO SPECIFY 1 HOUR FIRE RATED ASSEMBLY FOR THE
 WEST WALL WITH FIRE EXPOSURE FROM BOTH SIDES AS
 REQUIRED BY TABLE R302.1(1). ASSEMBLY NEED TO TESTED IN
 ACCORDANCE WITH ASTM E 119 OR UL 263.
  
 C) GUEST BEDROOM WINDOW ABOVE GARAGE DOESN'T COMPLY
 WITH THE EGRESS REQUIREMENTS OF SEC. R310
 FBC-RESIDENTIAL 5TH EDITION (2014). NEED TO COMPLY WITH
 THE MIN. CLEAR HEIGHT AND TOTAL CLEAR OPENING. REVISE
 AS REQUIRED.
  
 4- THE WIDTH OF THE NEW GUEST HOUSE STAIRWAY DOESN'T
 COMPLY WITH SEC. R311.7.1 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 5- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE GUEST ROOM ABOVE AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL. SPECIFY THE DOOR MATERIAL, FIRE RATING
 AND EQUIPPED WITH SELF CLOSING DEVICE.
  
 6- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN ROOF
 TILE ADHESIVE PRODUCT APPROVAL IS REQUIRED. SEE ROOF
 TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. NOTE:
 PROVIDE SPECIFIC FASTENING METHOD. PER CODE OR PER
 PRODUCT APPROVAL IS NOT ACCEPTED AS SHOWING COMPLIANCE.
  
 7- BUILDING SECTION AT MAIN HOUSE 2/A2.1 SHOWS A
 STAIRWAY WITH OPEN RISERS. OPEN RISERS ARE NOT ALLOWED
 UNLESS THEY COMPLY WITH SEC. R311.7.5.1
 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL STAIRS, HANDRAILS AND GUARDRAILS
 (INCLUDING BALCONY GUARDRAILS) SHOWING COMPLIANCE WITH
 THE LIVE LOADS OF TABLE R301.5 AND ALL THE REQUIREMENTS
 OF SEC. R311.7.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE NEW SCREEN ENCLOSURE IN THE OPEN
 LOGGIA. SPECIFY ALL FRAMING MEMBERS AND FASTENERS AND
 PROVIDE MESH SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 10- REVISE DESIGN CRITERIA SPECIFIED ON THE RIGHT
 BOTTOM OF SHEET A3.1. WINDOW OPENINGS HAVE A TRIBUTARY
 AREA SMALLER THAN 20 SQ.FT. REVISE AS REQUIRED. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 11- TYP WALL SECTION @ NEW ADDITION 3/A4.1:
 A) DOESN'T MATCH PROPOSED CONSTRUCTION. THIS IS WOOD
 FRAMED CONSTRUCTION. THERE IS A LOT OF INFORMATION THAT
 APPLIES ONLY TO CONCRETE BLOCK CONSTRUCTION. REVISE AS
 REQUIRED TO MATCH PROPOSED CONSTRUCTION. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL.
  
 12- WALL SECTION @ OUTDOOR PORCH & BALCONY 2/A4.1:
 A) REVISE THE ROOF SLOPE SHOWN AT HE BALCONY TO COMPLY
 WITH SEC. R905 FBC-RESIDENTIAL.
  
 B) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL. ALSO, FRAMING SHOWN AT TOP OF
 THE WINDOW IS NOT CLEAR. REVISE AS REQUIRED.
  
 13- WALL SECTION @ MAIN HOUSE STAIRWELL 1/A4.1:
 A) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL. ALSO, FRAMING SHOWN AT TOP AND
 BOTTOM OF THE WINDOW IS NOT CLEAR. REVISE AS REQUIRED.
  
 B) ROOF SHEATHING NOTE IS REPEATED 3 TIMES. PROVIDE
 CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- WALL SECTIONS @ GARAGE 4/S2 AND 5/S2 ON SHEET S2:
 A) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL.
  
 B) MISSING THE FOOTING INFORMATION AT ALL BEARING
 WALLS. SEC. R301.1 FBC-RESIDENTIAL. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS. COORDINATE WITH THE
 FOUNDATION PLAN.
  
 15- SIZE OF STEEL BEAM SPECIFIED ON SHEET S3 IS NOT
 CLEAR. DIMENSIONS SPECIFIED ON THE STEEL BEAM SCHEDULE
 AND DETAIL 8E/S3 DON'T MATCH. ALSO, GIVEN DIMENSIONS
 DON'T CORRESPOND TO W10X49 STEEL BEAM. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 16- CLEARLY COORDINATE DETAILS 8A THRU 8E WITH FLOOR
 FRAMING PLANS AND ALL SCHEDULES SHOWN ON SHEET S3. .
 CLEARLY IDENTIFY ALL BEAM TYPES, COLUMN TYPES AND SIZES
 AND COORDINATE WITH ALL L FRAMING PLANS. CLEARLY
 SPECIFY THE WOOD HEADERS AT ALL OPENINGS. SEC. R301.1
 FBC-RESIDENTIAL. NOTE: ALSO VERIFY THICKNESS OF COLUMNS
 SUPPORTING THE STEEL BEAM (SEE COLUMN SCHEDULE AND
 DETAIL 83/S3. ALSO, SPECIFY COLUMNS SUPPORTING THE WB-4
 BEAM ON THE GUEST HOUSE. CLEARLY IDENTIFY EACH COLUMN
 AND BEAM SHOWN ON FRAMING PLANS.
  
 17- PLAN DETAIL AT "OHGD' DETAIL 6/A4 ON SHEET S3:
 CLEARLY SPECIFY ALL FASTENERS AND SIZE OF STRUCTURAL
 BUCK THAT IS GOING TO SUPPORT THE LOADS FROM THE GARAGE
 DOOR. SEC. R301.1 FBC-RESIDENTIAL.
  
 18- DETAIL 8E/S3: CLEARLY SPECIFY THE FRAMING
 CONNECTION FROM ALL STRUCTURAL MEMBERS THAT ARE
 ATTACHED TO THE STEEL BEAM. (FLOOR JOIST, ON BOTH SIDES
 AND WOOD FRAME BEARING WALL-ABOVE). SEC. R301.1
 FBC-RESIDENTIAL.
  
 19- THIS PROJECT IS NOT AN ALTERATION LEVEL 2. THIS IS
 ALTERATION LEVEL 3 AND ADDITION. REVISE INFORMATION ON
 SHEET T1 AS REQUIRED. SEC. 505 AND SEC. 507
 FBC-EXISTING BUILDING.
  
 20- PROPOSED 1ST FLOOR PLAN ON SHEET A1.2: MISSING
 GUARDRAIL INFORMATION BY THE NEW STAIRWAY. PROVIDE
 COMPLETE INFORMATION SHOWING COMPLIANCE WITH SEC.
 R312.1.1 FBC-RESIDENTIAL.
  
 21- FIRST FLOOR FOUNDATION & FRAMING PLAN ON SHEET S1:
 NEW FLOOR JOIST BY THE KITCHEN AREA ADDITION ARE
 RESTING ON THE AIR. PROVIDE COMPLETE INFORMATION
 SHOWING THE BEAMS AND SUPPORTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 22- SECOND FL. FLOOR FRAMING PLAN ON SHEET S1: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE BEARING
 WALL SHOWN IN THE MIDDLE OF THE NEW MASTER BEDROOM AND
 MASTER BATHROOM. SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 CLARIFY WHY THE SAME WALL (NOT SHOWN AS HATCHED) IS
 SHOWN ON THE ROOF FRAMING PLAN?.
  
 23- PROVIDE COMPLETE SPECIFICATIONS FOR ALL THE FRAMING
 MEMBERS AND CONNECTORS FOR OVERHANG DETAIL/SECTION 6/S2
 ON SHEET S2. SEC. R301.1 FBC-RESIDENTIAL.
  
 24- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R16
 SUBMITTED;
 A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FC-RESIDENTIAL.
  
 B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. SEE NOTE #8
 ON PAGE 2 OF 58 OF FLORIDA PRODUCT APPROVAL SUBMITTED.
  
 25- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF DECK ZONES.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16. NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 D) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD ON SHEET A3.2.
 NOA 16-0617.07 SUBMITTED DOESN'T MEET THOSE DESIGN
 PRESSURES.
  
 E) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT
 RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS
 FOR SMALL MISSILE IMPACT RESISTANT.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
  
 G) FIXED WINDOWS AS SPECIFIED ON PLANS.
  
 H) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 26- ARCHITECT OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 27- PROVIDE DETAILS AND SPECIFICATIONS FOR THE GARAGE
 AND DWELLING SEPARATION AS REQUIRED BY TABLE R302.6
 FBC-RESIDENTIAL.
  
 28- ENERGY CALCULATIONS SUBMITTED. THIS IS A
 CONTRIBUTING HISTORIC HOUSE (BOTH BUILDINGS). ENERGY
 CALCULATIONS ARE NOT REQUIRED, BUT IF CONTRACTOR WANTS
 TO SUBMIT THEM, THEN THE FOLLOWING REVISIONS ARE
 REQUIRED (SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014):
 MAIN HOUSE: (A) PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, INCLUDING OWNER'S NAME, BUILDER'S NAME, ETC. (B)
 THIS IS NOT NEW CONSTRUCTION. (C) CEILING INSULATION
 R-VALUE DOESN'T MATCH PLANS. (D) PROVIDE THE NAME OF
 THE PERSON WHO PREPARED THE CALCULATIONS. (E)REVISE #
 OF OCCUPANTS. (F)REVISE ROOF MATERIAL TO MATCH PLANS.
 (G)REVISE DOOR INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVAL. (H) WINDOWS OVERHANG DEPTH AND SEPARATION
 DON'T MATCH PLANS. (I)BUILDER TO COMPLETE THE EPL
 DISPLAY CARD.
 GUEST HOUSE: (A) PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, INCLUDING OWNER'S NAME, BUILDER'S NAME, ETC. (B)
 CEILING INSULATION R-VALUE DOESN'T MATCH PLANS. (C)
 PROVIDE THE NAME OF THE PERSON WHO PREPARED THE
 CALCULATIONS. (D) THERE IS NOT KITCHEN IN THE GUEST
 HOUSE. (E) REVISE ROOF MATERIAL TO MATCH PLANS. (F)
 REVISE DOOR INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVAL. (G) WINDOWS INFORMATION DON'T MATCH PLANS.
 (H)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. (I)BUILDER TO COMPLETE THE EPL DISPLAY CARD. (J)
 GARAGE AREA DOESN'T MATCH PLANS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]