Plan Review Notes
Plan Review Notes For Permit 17010585
Permit Number 17010585
Review Stop M
Sequence Number 1
Notes
Date Text
2017-01-30 12:08:331ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010585
 1/30/17
  
 1) THE PLAN INDICATES A DUCT PENETRATING THE INTERIOR
 EXIT STAIRWELL ENCLOSURE- SEE SECTION 1022.5 FBC-14
 BUILDING AND RELOCATE THE DUCT.
  
 2) PROVIDE AC CALCULATIONS FOR THE NEW MINI-SPLIT
 SYSTEM PER SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 AHU-1.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE NEW CU-1
 ON THE EXISTING RACK- SECTION 301.15.
  
 5) SHOW THE REQUIRED RETURN AIR TRANSFERS FROM ROOMS
 WITH FULL HEIGHT PARTITIONS- SECTION 601.5
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER