Plan Review Notes For Permit 17010585 |
Permit Number |
17010585 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-30 12:08:33 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010585 | | 1/30/17 | | | | 1) THE PLAN INDICATES A DUCT PENETRATING THE INTERIOR | | EXIT STAIRWELL ENCLOSURE- SEE SECTION 1022.5 FBC-14 | | BUILDING AND RELOCATE THE DUCT. | | | | 2) PROVIDE AC CALCULATIONS FOR THE NEW MINI-SPLIT | | SYSTEM PER SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW | | AHU-1. | | | | 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE NEW CU-1 | | ON THE EXISTING RACK- SECTION 301.15. | | | | 5) SHOW THE REQUIRED RETURN AIR TRANSFERS FROM ROOMS | | WITH FULL HEIGHT PARTITIONS- SECTION 601.5 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|