Plan Review Notes
Plan Review Notes For Permit 17010580
Permit Number 17010580
Review Stop P
Sequence Number 2
Notes
Date Text
2017-03-15 09:57:381ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH SECOND REQUEST.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE INSTANT
 WATER HEATERS.WPB AMEND. TO FBC SEC. 107.2.1.
  
 3) SHT. P-002 - FL. ADMIN. CODE RULE 64E-6.013 (7) (A)
 REQUIRES A MINIMUM 4" OUTLET TEE ON THE GREASE
 INTERCEPTOR THAT EXTENDS TO WITHIN 8 INCHES OF THE
 BOTTOM OF THE TANK. THE DETAIL ON THE PLANS DOES NOT
 SHOW THIS. SUBMIT A CURRENT COPY OF THE STATE APPROVAL
 FOR THIS TANK FROM THE FLORIDA DEPARTMENT OF HEALTH.
  