Plan Review Notes
Plan Review Notes For Permit 17010580
Permit Number 17010580
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-30 10:18:181) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE INSTANT
 WATER HEATERS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-002 - WATER HEATER DETAIL - THE RELIEF LINE
 SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER. FBC-PLUMBING SEC.504.6 (2).
 3) SHT. P-002 - FL. ADMIN. CODE RULE 64E-6.013 (7) (A)
 REQUIRES A MINIMUM 4" OUTLET TEE ON THE GREASE
 INTERCEPTOR THAT EXTENDS TO WITHIN 8 INCHES OF THE
 BOTTOM OF THE TANK. THE DETAIL ON THE PLANS DOES NOT
 SHOW THIS. SUBMIT A CURRENT COPY OF THE STATE APPROVAL
 FOR THIS TANK FROM THE FLORIDA DEPARTMENT OF HEALTH.
 4) SHT.P-002 - PENETRATION DETAIL - THERE IS NO FLOOR
 PENETRATION DETAIL ON THE PLANS FOR A 3 INCH PVC PIPE.
 THERE IS CURRENTLY A 3 INCH PVC PIPE INSTALLED IN ROOM
 # 114 THAT PENETRATES THE 2ND FLOOR SLAB FOR A WATER
 CLOSET ON THE 2ND FLOOR IN ROOM #205. THE PVC PIPE IN
 THE FIELD HAS BEEN PAINTED WITH A BLACK FIRE RETARDANT
 PAINT. THERE ARE NO SPECIFICATIONS FOR THIS MATERIAL
 THAT HAS BEEN SUBMITTED TO ME FOR REVIEW NOR ARE THERE
 ANY DETAILS ON THE PLANS FOR THIS MATERIAL. ALSO, I
 HAVE NO DOCUMENTATION THAT THIS MATERIAL HAS BEEN
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.SUBMIT A LISTED PENETRATION DETAIL
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. WPB
 AMEND. TO FBC SEC. 107.21, 107..3.4.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW