Date |
Text |
2017-01-30 10:18:18 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE INSTANT |
| WATER HEATERS.WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) SHT. P-002 - WATER HEATER DETAIL - THE RELIEF LINE |
| SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| ROOM AS THE WATER HEATER. FBC-PLUMBING SEC.504.6 (2). |
| 3) SHT. P-002 - FL. ADMIN. CODE RULE 64E-6.013 (7) (A) |
| REQUIRES A MINIMUM 4" OUTLET TEE ON THE GREASE |
| INTERCEPTOR THAT EXTENDS TO WITHIN 8 INCHES OF THE |
| BOTTOM OF THE TANK. THE DETAIL ON THE PLANS DOES NOT |
| SHOW THIS. SUBMIT A CURRENT COPY OF THE STATE APPROVAL |
| FOR THIS TANK FROM THE FLORIDA DEPARTMENT OF HEALTH. |
| 4) SHT.P-002 - PENETRATION DETAIL - THERE IS NO FLOOR |
| PENETRATION DETAIL ON THE PLANS FOR A 3 INCH PVC PIPE. |
| THERE IS CURRENTLY A 3 INCH PVC PIPE INSTALLED IN ROOM |
| # 114 THAT PENETRATES THE 2ND FLOOR SLAB FOR A WATER |
| CLOSET ON THE 2ND FLOOR IN ROOM #205. THE PVC PIPE IN |
| THE FIELD HAS BEEN PAINTED WITH A BLACK FIRE RETARDANT |
| PAINT. THERE ARE NO SPECIFICATIONS FOR THIS MATERIAL |
| THAT HAS BEEN SUBMITTED TO ME FOR REVIEW NOR ARE THERE |
| ANY DETAILS ON THE PLANS FOR THIS MATERIAL. ALSO, I |
| HAVE NO DOCUMENTATION THAT THIS MATERIAL HAS BEEN |
| REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE.SUBMIT A LISTED PENETRATION DETAIL |
| APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. WPB |
| AMEND. TO FBC SEC. 107.21, 107..3.4.2. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |