Plan Review Notes
Plan Review Notes For Permit 17010580
Permit Number 17010580
Review Stop M
Sequence Number 1
Notes
Date Text
2017-01-25 16:28:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010580
 1/25/17
  
 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BE SIGNED
 AND DATED BY THE OWNER/AGENT- SEE PAGE #3.
  
 2) THE AC COOLING AND HEATING CALCULATIONS FOR AHU-16
 WERE NOT SUBMITTED- PLEASE PROVIDE.
  
 3) SHEET M-101: THERE IS A O/A WALL CAP FOR AHU'S 2 & 3
 SHOWN IN THE MIDDLE OF THE FOYER, WHICH APPEARS TO BE A
 TYPO. PLEASE INDICATE HOW THE O/A IS BEING SUPPLIED TO
 THE AHU'S AND THE TOTAL AMOUNT OF O/A CFMS SUPPLIED.
  
 4) THE O/A CFMS SHOWN IN THE IAQ PROCEDURE FOR EACH
 AHU, AND THE TOTAL FOR ALL AHU'S DOES NOT MATCH THE O/A
 CFMS LISTED IN THE SCHEDULE ON SHEET M-001, OR THE CFMS
 SHOWN ON THE LAYOUT PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  