2017-01-25 16:28:51 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010580 | | 1/25/17 | | | | 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BE SIGNED | | AND DATED BY THE OWNER/AGENT- SEE PAGE #3. | | | | 2) THE AC COOLING AND HEATING CALCULATIONS FOR AHU-16 | | WERE NOT SUBMITTED- PLEASE PROVIDE. | | | | 3) SHEET M-101: THERE IS A O/A WALL CAP FOR AHU'S 2 & 3 | | SHOWN IN THE MIDDLE OF THE FOYER, WHICH APPEARS TO BE A | | TYPO. PLEASE INDICATE HOW THE O/A IS BEING SUPPLIED TO | | THE AHU'S AND THE TOTAL AMOUNT OF O/A CFMS SUPPLIED. | | | | 4) THE O/A CFMS SHOWN IN THE IAQ PROCEDURE FOR EACH | | AHU, AND THE TOTAL FOR ALL AHU'S DOES NOT MATCH THE O/A | | CFMS LISTED IN THE SCHEDULE ON SHEET M-001, OR THE CFMS | | SHOWN ON THE LAYOUT PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|