Plan Review Notes
Plan Review Notes For Permit 17010523
Permit Number 17010523
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-31 05:59:221) INDICATE THE OCCUPANT LOAD ON THE PLANS IN
 COMPLIANCE WITH FBC-BUILDING TABLE 1004.1.
 2) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL COMPLY WITH 2014
 FBC-BUILDING SEC.1210.2.2.
 3) SHT. A1.4 - D6 - THE GRAB BARS SHALL BE MEASURED TO
 THE TOP OF THE GRIPPING SURFACE. 2014 FBC-ACCESSIBILITY
 SEC. 609.4.
 4) SHT.A1.4- DETAIL 6 - THE KNEE AND TOE CLEARANCE
 SPACE UNDER THE ACCESSIBLE LAVATORY SHALL CCOMPLY WITH
 2014 FBC-ACCESSIBILITY SEC. 306.
 5) SUBMIT MANUFACT. SPECIFICATIONS FOR THE CONDENSATE
 PUMP. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P2.1 - KEYNOTE #2 NOTES THE CONDENSATE BRANCH
 AS 1 1/2 INCH AND THE CONDENSATE PUMP LAYOUT SHOWS A 2
 INCH HEADER. CLARIFY. THE PLAN DOES NOT SHOW THE 2 INCH
 HEADER.
 7) ALL COFFEE MAKERS & ICE MAKERS SHALL BE EQUIPPED
 WITH BACKFFLOW PREVENTERS PER 2014 FBC-PLUMBING
 SEC.608.3, 608.16.10.
 8) SHT.P5.1 - SHOWS A SINK ON A WET VENT WHICH IS NOT
 PERMITTED PER 2014 FBC-PLUMBING SEC.912.1. AN
 INDIVIDUAL VENT ON THE MOP SINK WWILL CORRECT THIS
 ISSUE.
 9) SHT. P5.1 - WATER RISER - MEN'S RESTROOM #135 - IT
 APPEARS THAT ONLY ONE WC-1 IS SHOWN ON THE WATER RISER.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW