Plan Review Notes
Plan Review Notes For Permit 17010523
Permit Number 17010523
Review Stop M
Sequence Number 1
Notes
Date Text
2017-01-31 10:15:151ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010523
 1/31/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND PROVIDE MOTORIZED DAMPERS FOR EACH O/A
 DUCT SUPPLYING THE HEAT PUMPS.
  
 3) PROVIDE A SEQUENCE OF OPERATION FOR THE DS
 DETECTORS. CLARIFY IF ALL FANS ARE LINKED TOGETHER FOR
 SIMULTANEOUS FAN SHUTDOWN UPON ANY ONE DETECTOR
 ACTIVATING.
  
 4) THE MIAMI-DADE NOA #13-1017.09 CALLED OUT ON M&-2
 HAS BEEN SUPERSEDED BY NOA #15-0902.05. PLEASE SUBMIT
 TWO COPIES WITH ALL APPLICABLE INSTALLATION DETAILS
 MARKED OR HIGHLIGHTED, AND SHOP DRAWING APPROVAL STAMPS
 BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  