Plan Review Notes
Plan Review Notes For Permit 17010523
Permit Number 17010523
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-02 11:26:33PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 ELECTRIC RISER PLAN DETAISL ARE INCOMPLETE ON THE PLANS
 AND REQUIRE CLARIFICATION. FOUR NEW PANEL BOARDS ARE
 SHOWN ONLY TWO HAVE BEEN IDENTIFIED. PANEL A ON THE
 RISER PLAN IS IDENTIFIED AS EXISTING BUT DRAWN AS NEW
 AND WITHOUT FEEDER DETAILS. DETAILS AND LOCATION FOR
 PANEL ELP SEEM TO BE MISSING. FEEDER AND OVERCURRENT
 DETAILS FOR THE EXISTING PANELS ARE MISSING. NEC 215.5
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER