2017-02-21 11:01:43 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17010483 |
| ADD: 625 N. FLAGLER DR. #100 |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-615-3903 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JAN. 27/2017 |
| ACTION: BUILDING PROVISO |
| |
| SHOP DRAWINGS ARE TO BE SUBMITTED, TO BE REVIEWED BY |
| THE DESIGNER OF RECORD, AND SHOP DRAWING STAMP OF |
| APPROVAL FOR AN APPROVED REVIEW, BEFORE BEING SUBMITTED |
| TO THE CITY BUILDING DEPARTMENT. |
| |
| 1A) BUILDING PROVISO: THE PLANS DO NOT INDICATE THE |
| ENERGIES DEVELOPED BY THE X-RAY UNIT. FOR UNITS THAT |
| UTILIZING X-RAY ENERGIES OF 200 KEV AND ABOVE FOR |
| DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE SUBMITTED |
| TO THE DEPARTMENT OF HEALTH FOR REVIEW AND APPROVAL. |
| |
| 1B) BUILDING PROVISO: 2014 FBC-B 465.1.3. FOR X-RAY |
| UNITS THAT UTILIZE ENERGIES OF 200 KEV AND ABOVE THE |
| REQUIREMENTS OF FBC-B 465.1.3 (465.1.3.1- 465.5.1.3.3) |
| MUST BE OBSERVED. FOR UNITS THAT USE LESS ENERGY THAN |
| 200 KEV THEN THE MANUFACTURERS SPECIFICATIONS MUST BE |
| MET. |
| |
| 2) BUILDING PROVISO: SHEET A1.11 THE FLOOR PLAN |
| INDICATES THE DOOR INTO THE X-RAY ROOM IS IDENTIFIED AS |
| NUMBER 028. THE DOOR SCHEDULE LIST THE LOCK AS |
| MANUFACTURER FALCON T511P6 DANE A LEVER LOCK. PLEASE |
| REVIEW THE REQUIREMENTS FOUND IN SECTION: |
| 465.6 OF THE 2014 FBC-B. DOORS, INTERLOCKS, AND WARNING |
| SYSTEMS. |
| |
| 2A) 465.6.1 A LICENSEE SHALL CONTROL ACCESS TO THE |
| TELETHERAPY ROOM BY A DOOR AT EACH ENTRANCE. |
| |
| 2B) 465.6.2 A LICENSEE SHALL EQUIP EACH ENTRANCE TO THE |
| TELETHERAPY ROOM WITH AN ELECTRICAL INTERLOCK SYSTEM |
| THAT SHALL: |
| |
| 2C) 465.6.2.1. PREVENT THE OPERATOR FROM TURNING ON THE |
| PRIMARY BEAM OF RADIATION UNLESS EACH TREATMENT ROOM |
| ENTRANCE DOOR IS CLOSED; |
| |
| 2D) 465,6,2,2. TURN OFF THE BEAM OF RADIATION |
| IMMEDIATELY WHEN AN ENTRANCE DOOR IS OPENED; AND |
| |
| 2E) 465.6.2.2. 3. PREVENT THE PRIMARY BEAM OF RADIATION |
| FROM BEING TURNED ON FOLLOWING AN INTERLOCK |
| INTERRUPTION UNTIL ALL TREATMENT ROOM ENTRANCE DOORS |
| ARE CLOSED AND THE BEAM ON-OFF CONTROL IS RESET AT THE |
| CONSOLE. |
| |