2017-01-25 12:52:42 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010483 | | 1/25/17 | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) PROVIDE VENTILATION FOR THE THE SOILED AND CLEAN | | ROOMS- SECTION 502.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|