2017-01-19 13:34:50 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES | | A SPECIFIC ELECTRICAL WIRING METHOD THAT PROVIDES | | REDUNDANT GROUNDING AND INCLUDES AN INSULATED COPPER | | EQUIPMENT GROUND. NEC 517.13 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-805-6654 | | 561-373-3701 | | [email protected] | | | | | | |
|