Plan Review Notes
Plan Review Notes For Permit 17010482
Permit Number 17010482
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-27 12:22:381) TOILET ROOMS #204 AND #205 SHALL HAVE HANDICAPPED
 ACCESSIBLE TOILET COMPARTMENTS LOCATED WITHIN THE
 RESTROOMS PER THE 2014 FBC- ACCESSIBILITY SEC.213.3.1.
 THE TOILET COMPARTMENT DIMENSIONS SHALL COMPLY WITH
 2014 FBC - ACCESS. SECS. 305, 604.
 2) A LAVATORY SHALL BE LOCATED WITHIN EACH REQUIRED
 TOILET COMPARTMENT PER THE 2014 FBC SEC.604.8.1.6.
 3) SHOW THE CLEAR INSIDE DIMENSIONS OF ALL TOILET
 ROOMS. ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS. 604.3 FOR WATER CLOSETS AND
 SEC.606.2 FOR LAVATORIES.
 4) A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE
 CENTERED ON THE FIXTURE IS REQUIRED FOR THE BREAK ROOM
 SINK. COMPLY WITH FBC-ACCESS. SEC.606.2.
 5) THE ACCESSIBLE DRINKING FOUNTAIN LOCATED IN CORRIDOR
 # 206 SHALL COMPLY WITH 2014 FBC- ACCESS. SEC.307.2 FOR
 PROTRUSION LIMITS.
 6) SHT. A4.22 - REFERENCED IS MADE TO THE 2010 FBCA.
 THE CODEE IN EFFECT IS THE 2014 FBC.
 7) SHT. A4.23 - THE HEIGHT OF THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014
 FBC SEC.609.4.
 8) THE MAXXIMUM REACH RANGE HEIGHT FOR THE PAPER TOWEL
 DISPENSER SHALL COMPLY WITH 2014 FBC - ACCESS. SEC.308.
 9) SHOW THE CAPACITY OF THE EXPANSION TANK ON THE WATER
 HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT. P5.1 - SIZE ALL VENTS ON THE SANITARY RISER.
 COMPLY WITH 2014 FBC-PLUMBING SEC.906.1.
 11) THE VENT FOR THE TWO MOST UPSTREAM WATER CLOSETS ON
 THE SANITARY RISER ( TOILET ROOMS 204 & 205 ) SHALL BE
 TAKEN OFF BETWEEN THE WATER CLOSETS . 2014 FBC-PLUMBING
 SEC.901.2, 905.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  