2017-01-27 12:22:38 | 1) TOILET ROOMS #204 AND #205 SHALL HAVE HANDICAPPED |
| ACCESSIBLE TOILET COMPARTMENTS LOCATED WITHIN THE |
| RESTROOMS PER THE 2014 FBC- ACCESSIBILITY SEC.213.3.1. |
| THE TOILET COMPARTMENT DIMENSIONS SHALL COMPLY WITH |
| 2014 FBC - ACCESS. SECS. 305, 604. |
| 2) A LAVATORY SHALL BE LOCATED WITHIN EACH REQUIRED |
| TOILET COMPARTMENT PER THE 2014 FBC SEC.604.8.1.6. |
| 3) SHOW THE CLEAR INSIDE DIMENSIONS OF ALL TOILET |
| ROOMS. ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH 2014 |
| FBC-ACCESSIBILITY SECS. 604.3 FOR WATER CLOSETS AND |
| SEC.606.2 FOR LAVATORIES. |
| 4) A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE |
| CENTERED ON THE FIXTURE IS REQUIRED FOR THE BREAK ROOM |
| SINK. COMPLY WITH FBC-ACCESS. SEC.606.2. |
| 5) THE ACCESSIBLE DRINKING FOUNTAIN LOCATED IN CORRIDOR |
| # 206 SHALL COMPLY WITH 2014 FBC- ACCESS. SEC.307.2 FOR |
| PROTRUSION LIMITS. |
| 6) SHT. A4.22 - REFERENCED IS MADE TO THE 2010 FBCA. |
| THE CODEE IN EFFECT IS THE 2014 FBC. |
| 7) SHT. A4.23 - THE HEIGHT OF THE GRAB BARS SHALL BE |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014 |
| FBC SEC.609.4. |
| 8) THE MAXXIMUM REACH RANGE HEIGHT FOR THE PAPER TOWEL |
| DISPENSER SHALL COMPLY WITH 2014 FBC - ACCESS. SEC.308. |
| 9) SHOW THE CAPACITY OF THE EXPANSION TANK ON THE WATER |
| HEATER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) SHT. P5.1 - SIZE ALL VENTS ON THE SANITARY RISER. |
| COMPLY WITH 2014 FBC-PLUMBING SEC.906.1. |
| 11) THE VENT FOR THE TWO MOST UPSTREAM WATER CLOSETS ON |
| THE SANITARY RISER ( TOILET ROOMS 204 & 205 ) SHALL BE |
| TAKEN OFF BETWEEN THE WATER CLOSETS . 2014 FBC-PLUMBING |
| SEC.901.2, 905.3. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |